GEM0650/0956/1256 A/W | Operation: Performance |
Beginning at the compressor, the refrigerant is compressed into a high temperature gas. The discharge line directs this gas to the condenser. At the condenser (air or water cooled) the gas is cooled by either air or water and then it condenses into a liquid.
This high pressure liquid then goes through the liquid line to the expansion valve. The thermostatic expansion valve meters liquid refrigerant into the evaporator, the volume of liquid refrigerant depending upon the temperature of the evaporator.
At the evaporator, the refrigerant enters an area of relatively low pressure, where it can easily “boil off” or evaporate. As it evaporates, it absorbs heat from the evaporator and whatever is in contact with it (such as water inside it). After the evaporator, the refrigerant, now a low pressure vapor, goes through the suction line back to the compressor, where the cycle is repeated.
Typical Low Side Pressure: |
|
Air Cooled: | |
Water Cooled: | 32 PSIG |
Typical Discharge Pressure: |
|
Air Cooled: | |
Water Cooled: | 245 PSIG |
Typical Compressor Amp Draw: |
|
GEM0650 115/60/1 | |
GEM0655 230/50/1 | |
GEM0956 | |
GEM1256 | |
Typical Auger Drive Motor Amp Draw: |
|
GEM0650 115/60/1 | 3.1 to 3.8 Amps |
GEM0655 230/50/1 | 1.6 to 3.8 Amps |
GEM0956 | 1.6 to 1.8 Amps |
GEM1256 | 1.6 to 1.8 Amps |
Expansion Valve Superheat: | |
High Pressure Cut Out- Automatic Reset: | 450 PSIG |
Low Pressure Cut Out- Automatic Reset: | 15 PSIG |
Refrigerant Charge: R404A |
|
GEM0650 |
|
Air Cooled: | 24 ounces |
Water Cooled: | 19 ounces |
GEM0655 |
|
Air Cooled: | 24 ounces |
GEM0956 |
|
Air Cooled: | 30 ounces |
Water Cooled: | 22 ounces |
GEM1256 |
|
Air Cooled: | 36 ounces |
Water Cooled: | 24 ounces |
| Page 16 |