Electrical Installation Requirements - Model IWF030 (M-speed)
Only trained personnel should perform this
procedure. Use caution while servicing
machines with covers removed and power
applied.
W700
WARN ING
Boiler Fed/Steam Heat Electric Heat
Code
Volta ge
Cycle
Phase
Wire
Full Load
Amps
Recommended
Circuit Breaker
(US-market)
AWG/mm 2
kW Standard
Heating Elements
Full Load
Amps
Recommended
Circuit Breaker
(US-market)
AWG/mm 2
US NON-US US NON-US
N 440-480 50/60 3 3+PE 4 10 10 14/2.5
6x2 kW
21 30 30 10/6.0
P 380-415 50/60 3 3+N+PE 12 15 16 14/2.5 30 40 40 8/10.0
Q 200-240 50/60 3 3+PE 12 15 16 14/2.5 42 50 50 8/10.0
X 200-240 50/60 1/3 2/3+PE 12 15 16 14/2.5 N/A N/A N/A N/A
Alternative Electric Heat Options
N 440-480 50/60 3 3+PE
3x3 kW
+
3x2 kW
26 30 30 10/6.0
P 380-415 50/60 3 3+N+PE 34 40 40 8/10.0
Q 200-240 50/60 3 3+PE 50 60 60 6/16.0
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
N 440-480 50/60 3 3+PE
6x3 kW
30 40 40 8/10.0
P 380-415 50/60 3 3+N+PE 38 50 50 8/10.0
Q 200-240 50/60 3 3+PE 57 70 70 4/25.0
X 200-240 50/60 1/3 2/3+PE N/A N/A N/A N/A
Table 12