IRIS manual Using A Plc With Iris Flame, Monitor, LOW NOx APPLICATIONS, APPLICATION OF P522

Models: P522

1 40
Download 40 pages 16.44 Kb
Page 26
Image 26
USING A PLC WITH IRIS FLAME

IRIS MODEL P522 APPLICATION MANUAL

cies than oil burners, particularly the low NOx type

USING A PLC WITH IRIS FLAME

burners. UV type detectors work very well on natu-

MONITOR

ral gas, but they are not so good on oil flames, and

PLCs are inherently unsafe when used by them-

work poorly on pulverized coal flames.

selves.1, 2, 3. Schemes have been devised to make

 

LOW NOx APPLICATIONS

them safe – such as feeding outputs back to the in-

Since the advent of low NOx burners and combustion

puts to check the outputs; using multiple outputs in

series for redundancy; and using “watchdog timers”

techniques to reduce emissions, the application of flame

that presumably detect malfunctions. None of these

monitors has been radically changed (i.e., an infrared

methods will make a PLC critical control loop 100

flicker flame monitor will not discriminate between

per cent safe.

burners in boilers utilizing low NOx gas burners). This

 

is particularly true if FGR is being used. Only a UV

PLCs cannot and should not be used by themselves

flame monitor with a wide linear range (S506) can be

for burner control or burner management systems

used. In this type of application, UV radiation is spread

without external protective circuitry to make them 100

out all over the furnace; but the more intense radiation

per cent safe. The critical loops that must be pro-

is concentrated at the root of the flame envelope, so the

tected are the main fuel trip (MFT) functions; initial

flame monitor must be aimed at this zone.

burner/igniter light off; subsequent continued burner

On the other hand, a UV flame monitor will not work

firing with flame monitoring; and burner shutdown.

 

on a low NOx oil flame, because there is little UV

Most burner control systems are designed for over-

radiation detectable from this type of staged com-

all, fail safe operation. “Fail safe” means that, in the

bustion. Only an infrared flicker-type flame moni-

event of a failure of any component(s) or power, the

tor (S509, S512) will discriminate between burners.

burner or boiler will be shutdown safely. This usu-

The viewing head application tables (see Figure 11)

ally is accomplished by devices such as valves, so-

lenoids and relays that use springs to return them to

show most of the common applications and the view-

a safe state when energized.

ing heads recommended for them. If you have enqui-

 

ries regarding applications that are not listed, please

Burner control systems designed for power-to-open

contact Bob Langthorne at IRIS Systems Inc. for rec-

and power-to-close type systems are different because

ommendations.

of the storage battery backup upon loss of AC power.

APPLICATION OF P522

However, the philosophy of fail safe concepts and

safety with regard to critical loops is the same.

Great effort has gone into designing the P522 signal

The external, protective circuitry required for the

processor to make it fail safe. When properly in-

stalled and functioning as designed, it functions as a

boiler-common MFT function can be as simple as

safety device that will provide protection from boiler

using a single relay energized by a string of contacts

or furnace explosions.

in series that would include the usual permissives,

However, the output of the flame relay in most instal-

proper air flow, fuel pressure, fuel temperature, etc.

More elaborate designs involving the PLC for alarm-

lations is not used directly to control the fuel valves.

ing or prompts, in addition to diagnostic functions,

The circuitry used between the flame relay and the safety

will complicate the MFT circuitry, but the underly-

shutoff valve solenoid should be carefully examined.

ing philosophy must be to maintain an external, di-

For example: a condition where the flame

rect, fail-safe function.

 

relay of the P522 feeds only to a pro-

Also, consideration should be given to the air-purge

grammable logic controller (PLC), and

timing function. The dangerous condition occurs

the PLC controls the fuel valve, repre-

when the purge timer times out short of the required

sents a dangerous installation with the po-

time delay. One way to overcome this type of mal-

tential for a serious explosion.

 

 

 

Page 26

 

Page 26
Image 26
IRIS manual Using A Plc With Iris Flame, Monitor, LOW NOx APPLICATIONS, APPLICATION OF P522