IRIS MODEL P522 APPLICATION MANUAL
The BASIC BURNER START CIRCUIT shown in Figure 12 is a basic circuit requiring only two pieces of external hardware for each burner:
1.Master Relay with at least two nor-
2.DADE Timer, with two instant close/ timeout open contacts.
* * *
1.Bryant, Design of
2.Bryant, Is Your Plant’s Control Sys- tem Safe?, Power, August, 1979.
3Fischer, Are PLCs Suitable for Emer- gency
MODULE COMMUNICATIONS
The P522 communicates with any host computer that has an
MODBUS COMMUNICATION
Modbus Communication for IRIS P522 Flame Moni- toring System Signal Processor.
Introduction
Modbus Communication protocol allows the P522 to communicate with any process controllers or hu-
discrete registers. For more information on Modbus protocol, please refer to Modicon’s Modbus Proto- col Reference Guide
Communication Setting
P522 can communicate only in Modbus RTU mode, with the following configuration:
·9600 baud
·8 data bits
·no parity
·1 stop bit
The factory default of a P520/P522 station number is 0. It is important to change the station number so that there is no duplicate stations. To change or check the station number:
·Press and hold Reset button for 4 seconds.
·The 4 LED digits will show the baud rate and the station number. The 2 leftmost digits are the baud rate (96 or 48); the 2 rightmost digits are station number from (0 to 63).
·Press up/down button to change the station number.
·Press Store button to save station number.
Protocol Detect
P522 with firmware version 5.0 still supports the existing IRIS protocol. After
MODBUS RTU Function Supported
Four Modbus functions are supported:
·01 Output Coil Read
·03 Holding Register Read
·06 Preset Single Holding Register
·16 Preset Multiple Holding Register