IRIS MODEL P522 APPLICATION MANUAL
TABLE OF IRIS VIEWING HEADS AND PERFORMANCE WITH VARIOUS FUELS.
(DISC = discrimination between burners and flaming background*, SIG = signal strength)
GAS (HYDROGEN, PROPANE AND NATURAL GAS)
MODEL # | TYPE |
| COMMENTS | |
|
|
|
| |
S506 | UV | DISC excellent | SIG very good | |
|
|
|
| |
S509 | PbS Only | DISC good1 | SIG good | |
|
|
| ||
S509 | Si | NOT GOOD - WILL NOT SEE THIS FUEL | ||
|
|
|
| |
S511 | Ge | DISC fair | SIG good | |
|
|
|
| |
S512 | PbS | DISC good1 | SIG good | |
|
|
|
| |
S550 | UV & PbS | DISC excellent | SIG very good | |
|
|
|
| |
S552 | PbS Only | DISC good | SIG good | |
|
|
|
| |
S556 | UV Only | DISC excellent | SIG very good | |
|
|
|
| |
GAS LOW NOX BURNERS |
|
| ||
|
|
|
| |
MODEL # | TYPE |
| COMMENTS | |
|
|
|
| |
S506 | UV | DISC good | SIG good | |
|
|
|
| |
S509, | PbS Only | DISC none | SIG fair | |
S512 | ||||
|
|
| ||
|
|
|
| |
S550 | UV & PbS | DISC excellent | SIG very good | |
|
|
|
| |
S552 | PbS Only | DISC none | SIG fair | |
|
|
|
| |
S556 | UV Only | DISC excellent | SIG very good | |
|
|
|
|
FIGURE 11 - VIEWING HEAD APPLICATION TABLES
Page 27