IRIS MODEL P522 APPLICATION MANUAL
WIRING TO THE PLUG-IN TERMINALS
Figure 1 illustrates the
RF C refers to the common terminal of the flame relay, with ON being flame on, and OFF being flame off. You will note that there are two sets of contacts used for the flame relay.
SC C refers to the common terminal of the
-the hardware (i.e. the shutter mechanism in the viewing head, or the output relay itself);
-electronic components anywhere, or internal software in the P522; or
-the power to the unit is OFF – the most likely condition.
The main power feeds in through the terminals situ- ated on the upper left side (see GND, +26V and BAT). Each designated terminal is a double terminal, or pair, so that the wiring from the power supply can be “daisy chained” from one P522 to the next without having to twist wires together into one termination.
The pair designated BAT is for battery backup, if used. Note the rectifier used internally to prevent the 26 VDC main power supply from feeding into the battery. The backup battery, if used, should be 24 volts, to ensure that the 26 VDC power feeding the P522 will not feed back into the battery. In other words, no current will flow from the battery as long as voltage of the main power supply is above that of the battery. The negative side of the battery goes to the GND terminal on the left.
Figure 1 shows how these terminals are connected inside the P522. Note the two fuses marked F1 and F2. F1 is the main power fuse for the signal proces- sor as well as the viewing head(s), and is rated at .75 Amp. Fuse F2 feeds only to the viewing head(s),
and is rated at .25 Amp. On newer units (those with NO, CAL, and YES in red letters on the front panel) these fuses are
The viewing head terminals (bottom right) are iden- tified as V.H. A. and V.H. B. If only one viewing head is used, you must wire to the V.H. A. termi- nals. To the left of the viewing head terminals are two terminals marked V.H. SEL (viewing head se- lector relay). Energizing this connection with 19 to 38 VDC will cause the relay on this PC board to switch to viewing head B. The nominal voltage of this relay is 24V, but the 26 VDC power circuit can be used to switch this relay, if desired.
Only the viewing head signal wire (SIG) and the sig- nal ground wire (SIG GND) are switched with this changeover relay; the 26 VDC and power ground circuit is not disturbed. Make sure that the viewing head signal wire and signal ground (braided shield in the
The pair of terminals designated CHAN SEL (to the left of the V.H. SEL terminals) is used for selecting channel A or channel B on the P522. Energizing this pair of terminals causes the B channel to be se- lected. Polarity must be observed when wiring this connection (the positive terminal is on the right). This is an isolated input, so two wires are required. Any DC voltage from 7.5 to 30 may be used. The current required will depend upon the voltage, be- cause this is a photocoupler interface circuit with a 3900 ohm resistor feeding the LED light source.
For example: a 26 VDC voltage will result in a current flow of 25/3900 = .0064 Amp.
If flame is being detected and the channels are switched, the flame relay will remain energized for