SECTION 1: SPECIFICATION INFORMATION
JFT
Legend
1 -
(Floor drain - optional to either end)
2 - *Wash Tank Electrical Connection
3 - *Rinse Tank Electrical Connection
4 - *Booster Heater Electrical Connection
5 - *Motor Controls Electrical Connection
6 - 3/4" NPT Incoming Water Connection
7 - Condensate Connection - See Detail
Note:
The condensate removal system built into the dishmachine consists of a fan that will remove 1200 CFM. A single condensate connection must be provided by the installing contractor. This is an indirect connection that must be capable of removing 1200 CFM from the area.
| Condensate Exhaust Duct | |
18" [457mm] I.D. Square | Minimum 18" Square (Cross Section 324 Sq. In.) | |
Deep | Provided by HVAC Contractor | |
Exhaust Requirements | ||
| ||
3" [72mm] | - 1200 CFM | |
| ||
| Condensate duct to extended into duct pan. | |
| Condensate duct pan mounted on top of | |
| dishmachine electrical section. | |
|
JFT Series Technical Manual
Issued:
6