Johnson Controls 22 SEER UIM-B-0113, Johnson Controls Unitary Products, Error Codes - 18K 24K

Models: 22 SEER

1 46
Download 46 pages 60.74 Kb
Page 37
Image 37
TABLE 13: Error Codes - 18K 24K

898841-UIM-B-0113

TABLE 13: Error Codes - 18K 24K

 

 

 

 

 

 

Display Method of Outdoor

 

 

 

 

Display Method of Indoor Unit

Unit (Indicator has 3 kinds of

 

 

 

 

display status and they will

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

be repeated every 5s.)

 

 

 

Malfunction

 

 

 

 

 

 

 

 

 

 

No.

 

Indicator Display (during

 

OFF

 

A/C status

Possible Reasons

Name

 

 

 

 

Dual-8

 

blinking,

 

 

Illuminated

 

 

 

 

 

 

 

 

 

 

 

 

 

Code

ON 0.5s and OFF 0.5s)

 

Blink

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Display

 

 

 

 

 

 

 

 

 

 

 

Operation

Cool

Heating

D5

D6

D16

D30

 

 

 

 

 

Indicator

Indicator

Indicator

(D40)

(D41)

(D42)

(D43)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

During cooling and drying

Possible reasons:

 

High pressure

 

 

 

 

 

 

 

 

operation, except indoor fan

1. Refrigerant was overcharged;

 

 

OFF 3s and

 

 

 

 

 

 

operates, all loads stop

2. Poor heat exchange (including

1

protection

E1

 

 

blink once

 

 

operation. During heating

filth blockage of heat exchanger

 

of system

 

 

 

 

 

 

 

 

operation, the complete

and bad radiating environment);

 

 

 

 

 

 

 

 

 

 

unit stops.

Ambient temperature is too high.

 

 

 

 

 

 

 

 

 

 

 

 

 

Antifreezing

 

OFF 3S

 

 

 

 

 

 

During cooling and drying

1. Poor air-return in indoor unit;

2

 

 

 

 

 

 

 

operation, compressor and

E2

and blink

 

 

2. Fan speed is abnormal;

 

protection

 

twice

 

 

 

 

 

 

outdoor fan stop while indoor

3. Evaporator is dirty.

 

 

 

 

 

 

 

 

 

fan operates.

 

 

 

 

 

 

 

 

 

 

 

 

High discharge

 

 

 

 

 

 

 

 

During cooling and drying

Please refer to the ProficienTECH

 

 

OFF 3S

 

 

 

 

 

 

operation, compressor and

3

temperature

 

 

 

 

 

 

 

Ductless Splits Technical Training

E4

and blink

 

 

outdoor fan stop while indoor

 

protection of

 

4 times

 

 

 

 

 

 

fan operates. During heating

Manual (discharge protection,

 

compressor

 

 

 

 

 

 

 

overload).

 

 

 

 

 

 

 

 

 

operation, all loads stop.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF 3S

 

 

 

 

 

 

During cooling and drying

1. Supply voltage is unstable;

 

Overcurrent

 

 

 

 

 

 

 

operation, compressor and

4

 

 

 

 

 

 

 

2. Supply voltage is too low an

E5

and blink

 

 

outdoor fan stop while indoor

 

protection

 

5 times

 

 

 

 

 

 

fan operates. During heating

load is too high;

 

 

 

 

 

 

 

 

 

3. Evaporator is dirty.

 

 

 

 

 

 

 

 

 

 

operation, all loads stop.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF 3S

 

 

 

 

 

 

During cooling operation,

 

5

Communication

 

 

 

 

 

 

 

compressor stops while

Refer to the corresponding

E6

and blink 6

 

 

indoor fan motor operates.

ProficienTECH Ductless Splits

Malfunction

 

 

 

 

times

 

 

 

 

 

 

During heating operation,

Technical Training Manual.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the complete unit stops.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

High

 

OFF 3S

 

 

 

 

 

 

During cooling operation:

Refer to the ProficienTECH Duct-

 

 

 

 

 

 

 

 

compressor will stop while

less Splits Technical Training Man-

6

temperature

 

 

 

 

 

 

 

E8

and blink

 

 

indoor fan will operate.

ual

resistant

 

 

 

 

8 times

 

 

 

 

 

 

During heating operation,

(overload, high temperature

 

protection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

the complete unit stops.

resistant).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Circuit PG

 

 

 

 

 

 

 

 

 

 

 

motor (indoor

 

OFF 3S

 

 

 

 

 

 

Operation of remote

 

7

fan) has circuit

 

 

 

 

 

 

 

controller or control panel is

 

U8

and blink

 

 

 

 

 

 

Control board is damaged.

malfunction

 

 

 

 

 

 

available, but the unit wont

 

 

for 17 times

 

 

 

 

 

 

 

 

by zero cross

 

 

 

 

 

 

 

act.

 

 

 

 

 

 

 

 

 

 

 

 

detection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Poor connection for PGF in circuit

 

PG motor

 

OFF 3S

 

 

 

 

 

 

 

diagram;

8

(indoor fan

 

 

 

 

 

 

 

The complete unit will stop

Malfunction of indoor units control

H6

and blink

 

 

 

 

 

 

motor) does

 

 

 

 

 

 

operation.

panel AP1;

 

 

11 times

 

 

 

 

 

 

 

not operate

 

 

 

 

 

 

 

 

Malfunction of indoor units motor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M1.

 

 

 

 

 

 

 

 

 

 

 

 

 

Malfunction

 

OFF 3S

 

 

 

 

 

 

The complete unit will stop

Poor connection for the jumper cap

 

 

 

 

 

 

 

 

on indoor units control panel AP1;

9

protection of

C5

and blink

 

 

 

 

 

 

 

 

 

 

 

 

operation.

please reinsert or replace the

 

jumper cap

 

15 times

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

jumper cap;

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

During cooling and drying

1.Room temperature sensor hasn’t

 

Indoor ambient

 

 

 

 

 

 

 

 

been connected well with indoor

 

 

 

OFF 3S

 

 

 

 

 

operation, indoor unit

 

 

 

 

 

 

 

 

units control panel AP1 (refer to

10

temperature

 

 

 

 

 

 

 

operates while other loads

F1

 

and blink

 

 

 

 

 

the wiring diagram for indoor unit);

sensor is open/

 

 

 

 

 

 

will stop; during heating

 

 

 

once

 

 

 

 

 

2.Room temperature sensor is

 

short circuited

 

 

 

 

 

 

 

operation, the complete

 

 

 

 

 

 

 

 

 

damaged (please refer to the resis-

 

 

 

 

 

 

 

 

 

 

unit will stop operation.

 

 

 

 

 

 

 

 

 

 

tance table of temperature sensor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

During cooling and drying

1.Room temperature sensor hasn’t

 

Indoor evapora-

 

 

 

 

 

 

 

 

been connected well with indoor

 

 

 

OFF 3S

 

 

 

 

 

operation, indoor unit will

 

 

 

 

 

 

 

 

units control panel AP1 (refer to

11

tor temperature

 

 

 

 

 

 

 

operate while other loads

F2

 

and blink

 

 

 

 

 

the wiring diagram for indoor unit);

sensor is open/

 

 

 

 

 

 

will stop; During heating

 

 

 

twice

 

 

 

 

 

2.Room temperature sensor is

 

short circuited

 

 

 

 

 

 

 

operation, the complete

 

 

 

 

 

 

 

 

 

damaged (please refer to the resis-

 

 

 

 

 

 

 

 

 

 

unit will stop operation.

 

 

 

 

 

 

 

 

 

 

tance table of temperature sensor)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Outdoor

 

 

 

 

 

 

 

 

During cooling and drying

Outdoor temperature sensor

 

 

 

OFF 3S

 

 

 

 

 

operating, compressor stops

 

ambient

 

 

 

 

 

 

 

while indoor fan operates;

hasn’t been connected well or is

12

temperature

F3

 

and blink

 

damaged. Please check it by

 

 

During heating operation,

 

sensor is open/

 

 

3 times

 

 

 

 

 

the complete unit will stop

referring to the resistance table

 

short circuited

 

 

 

 

 

 

 

 

for temperature sensor).

 

 

 

 

 

 

 

 

 

operation.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Johnson Controls Unitary Products

37

Page 37
Image 37
Johnson Controls 22 SEER installation manual UIM-B-0113, Johnson Controls Unitary Products, Error Codes - 18K 24K