Action | Suction/Vapor | ||
| |||
| CLOSED |
| |
Evacuating with a |
|
| |
vacuum pump |
|
|
FULLY
OPEN
Outdoor unit running
FULLY
OPEN
Checking pressure and adding refrigerant
SUCTION/VAPOR
HOSE WITH
PUSH
REQUIRES FIELD PROVIDED 5/16” FEMALE
FLARE TO 1/4” MALE FLAREADAPTER.
VALVE CAP | OPEN POSITION |
| |
FLARE CAP |
|
| CLOSED POSITION |
| SCHRADER CORE |
TO LINE SET | SERVICE |
| |
| PORT |
| SERVICE |
| PORT CAP |
TO OUTDOOR UNIT | |
FLARE CAP |
|
| ALLEN WRENCH (5MM) |
| OPEN POSITION |
TO LINE SET CLOSED POISTION
TO OUTDOOR UNIT
FIGURE 38: Service Valve Operation
LEAK TEST AND EVACUATION
Air and moisture remaining in the refrigerant system will have undesir- able effects as indicated below:
1.Pressure in the system rises.
2.Operating current rises.
3.Cooling or heating efficiency drops.
4.Moisture in the refrigerant circuit may freeze and block capillary tubing (30 kBtu size only).
5.Water may lead to corrosion of parts in the refrigeration system.
The line set between the indoor and outdoor units must be leak tested and evacuated to remove any
AIR PURGING WITH VACCUM PUMP
COMPOUND
PRESSURE
GAUGE
HANDLE LOW
CHARGE HOSE
CONNECTING
PIPE
PACKED VALVE
AT LIQUID SIDE
PRESSURE GAUGE
MANIFOLD VALVE
HANDLE HIGH (KEEP FULL CLOSED)
CHARGE HOSE
VACUUM PUMP
ADAPTER FOR
PREVENTION
VACUUM
PUMP
Be sure to use a vacuum pump with
1.Run the vacuum pump.
2.Connect the charge hose from the manifold valve to the service port of the gas side packed valve.
3.Connect the charge hose to the port of the vacuum pump.
4.Open fully the low pressure side handle of the gauge manifold valve.
5.Operate the vacuum pump to begin evacuating.
6.The operation time for evacuation varies with the lineset length and capacity of the pump. Allow the pumpto operate until the system has been evacuated downto 300 microns. Allow the pump to con- tinue running foran additional 15 minutes.
7.Turn off the pump and leave the connection secured to the suction/ vapor
8.Close the low pressure valve handle of gauge manifold.
9.Open fully the valve stem of the packed valves (both gas and liquid sides).
10.Remove the charging hose from the service port.
11.Securely tighten the caps on the packed valves.
PACKED VALVE AT GAS SIDE
SERVICE PORT
SCHRADER CORE
FIGURE 39: Gauge Set Connections for Test Leaks, Evacuation Charging
ADDING REFRIGERANT FOR LONGER LINE SET
1.Open the low side manifold gauge valve and weigh in liquid refriger- ant. Use Table 6 to calculate the correct
2.Close manifold gauge valves.
LEAK TEST
Use the following procedure to test for system leaks:
1.Connect the manifold gauge set and dry nitrogen gas cylinder to the suction/vapor service port. See Figure 30.
2.Open valve on nitrogen cylinder.
3.Pressurize the system to no more than 150 PSIG with dry nitrogen.
4.Check for leaks using soapy water.
5.After the system is found to be free of leaks:
•Close valve on nitrogen cylinder
•Relieve the nitrogen pressure by: loosening the charge hose con- nector at the nitrogen cylinder.
•When the system pressure is reduced to normal, disconnect the hose from the cylinder.
Johnson Controls Unitary Products | 17 |