Johnson Controls 22 SEER Leak Test And Evacuation, Air Purging With Vaccum Pump, UIM-B-0113

Models: 22 SEER

1 46
Download 46 pages 60.74 Kb
Page 17
Image 17
LEAK TEST AND EVACUATION

898841-UIM-B-0113

Action

Shut-off

Suction/Vapor

2-way Valve

2-way Service Valve

 

 

CLOSED

 

Evacuating with a

 

 

vacuum pump

 

 

FULLY

OPEN

Outdoor unit running

FULLY

OPEN

Checking pressure and adding refrigerant

SUCTION/VAPOR

HOSE WITH 2-WAY SERVICE VALVE SCHRADER VALVE

PUSH

REQUIRES FIELD PROVIDED 5/16” FEMALE

FLARE TO 1/4” MALE FLAREADAPTER.

VALVE CAP

OPEN POSITION

 

FLARE CAP

 

 

CLOSED POSITION

 

SCHRADER CORE

TO LINE SET

SERVICE

 

 

PORT

 

SERVICE

 

PORT CAP

TO OUTDOOR UNIT

FLARE CAP

 

 

ALLEN WRENCH (5MM)

 

OPEN POSITION

TO LINE SETAIR PURGING WITH VACCUM PUMPADDING REFRIGERANT FOR LONGER LINE SETLEAK TESTManual background CLOSED POISTION

TO OUTDOOR UNIT

FIGURE 38: Service Valve Operation

LEAK TEST AND EVACUATION

Air and moisture remaining in the refrigerant system will have undesir- able effects as indicated below:

1.Pressure in the system rises.

2.Operating current rises.

3.Cooling or heating efficiency drops.

4.Moisture in the refrigerant circuit may freeze and block capillary tubing (30 kBtu size only).

5.Water may lead to corrosion of parts in the refrigeration system.

The line set between the indoor and outdoor units must be leak tested and evacuated to remove any non-condensable and moisture from the system.

AIR PURGING WITH VACCUM PUMP

COMPOUND

PRESSURE

GAUGE Manual background

-101kPa Manual backgroundManual background (-76cmHg) Manual background

HANDLE LOW Manual backgroundManual background

CHARGE HOSE Manual background

CONNECTING

PIPE

PACKED VALVEManual backgroundManual backgroundManual backgroundManual background

AT LIQUID SIDE

PRESSURE GAUGE

Manual background MANIFOLD VALVE

Manual backgroundManual background HANDLE HIGH Manual backgroundManual background (KEEP FULL CLOSED)

CHARGE HOSE

VACUUM PUMP

ADAPTER FOR

COUNTER-FLOW

PREVENTION

VACUUM

PUMP

Be sure to use a vacuum pump with counter-flow prevention function to make oil inside the pump does not flow back into the system pipes when the pump stops.

1.Run the vacuum pump.

2.Connect the charge hose from the manifold valve to the service port of the gas side packed valve.

3.Connect the charge hose to the port of the vacuum pump.

4.Open fully the low pressure side handle of the gauge manifold valve.

5.Operate the vacuum pump to begin evacuating.

6.The operation time for evacuation varies with the lineset length and capacity of the pump. Allow the pumpto operate until the system has been evacuated downto 300 microns. Allow the pump to con- tinue running foran additional 15 minutes.

7.Turn off the pump and leave the connection secured to the suction/ vapor 2-way service port. After five minutes, if the system fails to hold 500 microns or less, check all connections for tight fit and repeat the evacuation procedure.

8.Close the low pressure valve handle of gauge manifold.

9.Open fully the valve stem of the packed valves (both gas and liquid sides).

10.Remove the charging hose from the service port.

11.Securely tighten the caps on the packed valves.

Manual background PACKED VALVE AT GAS SIDE

Manual background SERVICE PORT

SCHRADER CORE

FIGURE 39: Gauge Set Connections for Test Leaks, Evacuation Charging

ADDING REFRIGERANT FOR LONGER LINE SET

1.Open the low side manifold gauge valve and weigh in liquid refriger- ant. Use Table 6 to calculate the correct weigh-in charge.

2.Close manifold gauge valves.

LEAK TEST

Use the following procedure to test for system leaks:

1.Connect the manifold gauge set and dry nitrogen gas cylinder to the suction/vapor service port. See Figure 30.

2.Open valve on nitrogen cylinder.

3.Pressurize the system to no more than 150 PSIG with dry nitrogen.

4.Check for leaks using soapy water.

5.After the system is found to be free of leaks:

Close valve on nitrogen cylinder

Relieve the nitrogen pressure by: loosening the charge hose con- nector at the nitrogen cylinder.

When the system pressure is reduced to normal, disconnect the hose from the cylinder.

Johnson Controls Unitary Products

17

Page 17
Image 17
Johnson Controls 22 SEER Leak Test And Evacuation, Air Purging With Vaccum Pump, Adding Refrigerant For Longer Line Set