SECTION VI: SPECIFICATIONS

898841-UIM-B-0113

DRAIN-WATER HOLE

BOTTOM FRAME

POWER SUPPLY AND INDOOR/OUTDOOR WIRE CONNECTION DRAIN PLUG

DRAIN CONNECTOR

HOSE (available commerially, inner dia. 0.63”)

FIGURE 4: Condensate Drainage

SECTION VI: SPECIFICATIONS

POWER SUPPLY AND INDOOR/OUTDOOR WIRE CONNECTION

The system should be powered from a dedicated circuit.

Wiring work should be based on applicable technical standards.

Wiring connections should be made following the provided diagrams.

Make sure all electrical connections are securely tightened.

TABLE 3: Air Conditioner Electrical Specifications

Solid conductor AWG14 or stranded conductor AWG14 are the MINI- MUM allowable wire sizes. There are some applications that will require larger gauge conductors depending on the voltage and amperage rat- ings on the data plate and the distance that the conductors will be routed. It is the installing contractor's responsibility to properly size the electrical conductors for the equipment and for the application.

All of the indoor units and outdoor units should have the electrical con- ductors sized using the National Electrical Code (NEC) and the local authority having jurisdiction whichever is more stringent. If the equip- ment is installed outside of the United States, all local codes within the country of origin must be followed.

The Ductless indoor units must have a minimum of 14 gauge, 600 volt double insulated copper conductors. The conductors for the indoor unit can be either solid or stranded copper. When possible the indoor unit should have stranded wire for the communication to ensure proper communication between the indoor and outdoor unit(s).

The Ductless outdoor units must have a minimum of 12 gauge, 600 volt double insulated copper conductors with the exception of the fol- lowing models: DHPM30CSM42Q1, DHPM36CSM42Q1, and DCPM36CSM42Q1, which require 10 gauge wire. The conductors for the outdoor unit should be solid or stranded copper conductors.

NOTICE

The listed wire sizes are only minimum requirements, as previously stated, the conductors for both indoor and outdoor units must be sized using the NEC and local authority having jurisdiction.

INDOOR UNIT

Air Conditioners

 

DCPM09NWM42Q1

DCPM09NWM41Q1

DCPM12NWM42Q1

DCPM12NWM41Q1

Power Supply (V, Phase, Hz)

208/230V/1

115V/1

208/230V/1

115V/1

Min. Circuit Ampacity

10

16

10

16

Fan Motor (F.L.A)

 

0.2

0.38

0.2

0.38

 

 

 

INDOOR UNIT

 

 

Air Conditioners

 

DCPM18NWM42Q1

DCPM24NWM42Q1

DCPM36NWM42Q1

 

Power Supply (V, Phase, Hz)

208/230V/1/60HZ

208/230V/1/60HZ

208/230V/1/60HZ

 

Min. Circuit Ampacity

16

16

17

 

Fan Motor (F.L.A)

 

0.28

0.24

0.4

 

 

 

 

OUTDOOR UNIT

 

 

Air Conditioners

 

DCPM09CSM42Q1

DCPM09CSM41Q1

DCPM12CSM42Q1

DCPM12CSM41Q1

Power Supply (V, Phase, Hz)

208/230V/1

115V/1

208/230V/1

115V/1

Max. Fuse Size (time delay) (A)

15

25

15

25

Min. Circuit Ampacity

10

16

10

16

Fan Motor (F.L.A)

 

0.14

0.17

0.14

0.17

Compressor

R.L.A

6.21

12.23

5.34

12.43

L.R.A

13.8

33

13.8

33

 

 

 

 

OUTDOOR UNIT

 

 

Air Conditioners

 

DCPM18CSM42Q1

DCPM24CSM42Q1

DCPM36CSM42Q1

 

Power Supply (V, Phase, Hz)

208/230V/1/60HZ

208/230V/1/60HZ

208/230V/1/60HZ

 

Max. Fuse Size (time delay) (A)

20

20

25

 

Min. Circuit Ampacity

16

16

17

 

Fan Motor (F.L.A)

 

0.32

1.1

0.45

 

Compressor

R.L.A

9.35

10.45

12.66

 

L.R.A

/

/

/

 

 

 