![Connecting Wires and the Ground Wire](/images/new-backgrounds/35823/3582311x1.webp)
TABLE 4: Heat Pump Electrical Specifications
INDOOR UNIT
Heat Pumps |
| DHPM09NWM42Q1 |
| DHPM09NWM41Q1 | DHPM12NWM42Q1 | DHPM12NWM41Q1 |
Power Supply (V, Phase, Hz) | 208/230V/1 |
| 115V/1 | 208/230V/1 | 115V/1 | |
Min. Circuit Ampacity |
| 10 |
| 16 | 10 | 16 |
Fan Motor (F.L.A) |
| 0.2 |
| 0.38 | 0.2 | 0.38 |
|
|
| INDOOR UNIT |
|
| |
Heat Pumps |
| DHPM18NWM42Q1 |
| DHPM24NWM42Q1 | DHPM30NWM42Q1 | DHPM36NWM42Q1 |
Power Supply (V, Phase, Hz) | 208/230V/1/60HZ |
| 208/230V/1/60HZ | 208/230V/1/60HZ | 208/230V/1/60HZ | |
Min. Circuit Ampacity |
| 16A |
| 16A | 15 | 23 |
Fan Motor (F.L.A) |
| 0.28A |
| 0.24A | 0.4 | 0.47 |
|
| OUTDOOR UNIT |
|
| ||
Heat Pumps |
| DHPM09CSM42Q1 |
| DHPM09CSM41Q1 | DHPM12CSM42Q1 | DHPM12CSM41Q1 |
Power Supply (V, Phase, Hz) | 208/230V/1 |
| 115V/1 | 208/230V/1 | 115V/1 | |
Max. Fuse Size (time delay) (A) | 15 |
| 25 | 15 | 25 | |
Min. Circuit Ampacity |
| 10 |
| 16 | 10 | 16 |
Fan Motor (F.L.A) |
| 0.14 |
| 0.17 | 0.14 | 0.17 |
Compressor | R.L.A | 6.21 |
| 12.23 | 5.34 | 12.43 |
L.R.A | 13.8 |
| 33 | 13.8 | 33 | |
|
| |||||
|
| OUTDOOR UNIT |
|
| ||
Heat Pumps |
| DHPM18CSM42Q1 |
| DHPM24CSM42Q1 | DHPM30CSM42Q1 | DHPM36CSM42Q1 |
Power Supply (V, Phase, Hz) | 208/230V/1/60HZ |
| 208/230V/1/60HZ | 208/230V/1/60HZ | 208/230V/1/60HZ | |
Max. Fuse Size (time delay) (A) | 20A |
| 20A | 25 | 35 | |
Min. Circuit Ampacity |
| 16A |
| 16A | 15 | 23 |
Fan Motor (F.L.A) |
| 0.32A |
| 1.1A | 0.45 | 0.73 |
Compressor | R.L.A | 9.35A |
| 10.45A | 11.42 | 16.95 |
L.R.A | / |
| / | / | / | |
|
|
Connecting Wires and the Ground Wire
•Use double insulated copper wire with 600V insulation.
•Use copper conductors only.
•Follow all local electrical codes.
Power Supply Cable and Ground Wire
•Use copper conductors only.
•Follow all local electrical codes.
NOTICE
The the indoor unit is powered from the outdoor unit, depending on local code, a disconnect switch needs to be installed to a power sup- ply circuit.
SECTION VII: REFRIGERANT LINE SET REQUIREMENTS
TABLE 5: Insulation Thickness & Material Information
•To prevent condensation, insulate the two refrigerant pipes.
•Refrigerant pipe bending radius must be 4 in. (100 mm) or more.
Be sure to use the insulation of specified thickness (refer to Table 5). Excessive insulation may cause incorrect installation of the indoor unit, and too little insulation may cause condensate to form.
•The unit has flared connections on both indoor and outdoor sides
•Remove the valve cover from the outdoor unit then connect the pipe
•Refrigerant pipes are used to connect the indoor and outdoor units
•Be careful not to crush or over bend the pipe in pipe bending
•Refrigerant adjustment
•If pipe length exceeds 25 ft. (7.5 m), additional refrigerant (R410A) charge is required (The outdoor unit is charged with refrigerant for pipe length up to 25 ft. [7.5 m]).
Pipe | Outside Diameter | Minimum Wall | Insulation | Insulation | |
Inch (mm) | Thickness | Thickness | Material | ||
| |||||
|
|
|
|
| |
Liquid Line | .375 (9.52) | 0.0315 (0.8) | 0.315 (8) | Heat Resistant Foam Plastic | |
Gas Line | .625 (15.9) | 0.0394 (1.0) | 0.315 (8) | 0.045 Specific Gravity | |
|
|
|
|
|
6 | Johnson Controls Unitary Products |