TABLE 21: J**DJ VOLTAGE LIMITATIONS1

349687-JTG-A-1007

TABLE 21: J**DJ VOLTAGE LIMITATIONS1

VOLTAGE LIMITATIONS

VOLTAGE

LIMITATIONS

POWER

VOLTAGE

SUPPLY

 

 

MIN.

MAX.

208/230-3-60

187

253

 

 

 

460-3-60

414

506

575-3-60

518

630

 

 

 

1.Utilization Range “A” in accordance with ARI Standard 110.

TABLE 22: PHYSICAL DATA

 

MODELS

 

J15DJ

J18DJ

 

J20DJ

J25DJ

 

 

 

 

 

 

 

 

 

 

EVAPORATOR

CENTRIFUGAL BLOWER (Dia. x Wd.)

 

15x15

18x15

 

18x15

18x15

BLOWER

FAN MOTOR HP

 

 

 

5.0

7.5

 

7.5

15

EVAPORATOR

ROWS DEEP

 

 

 

 

 

4

 

FINS PER INCH

 

 

 

 

 

13.5

 

COIL

 

 

 

 

 

 

FACE AREA (Sq. Ft.)

 

 

 

 

 

25

 

 

 

 

 

 

 

 

CONDENSER FAN

PROPELLER DIA. (In.)

(Each)

 

24

24

 

30

30

FAN MOTOR HP

(Each)

 

1/3

1/3

 

3/4

3/4

(Four Per Unit)

 

 

NOM. CFM TOTAL

(Each)

 

4,000

4,000

 

5,000

5,000

 

 

 

CONDENSER

ROWS DEEP

 

 

 

 

 

2

 

FINS PER INCH

 

 

 

 

 

20

 

COIL

 

 

 

 

 

 

FACE AREA (Sq. Ft.)

 

 

 

 

 

63.8

 

 

 

 

 

 

 

 

COMPRESSOR

SCROLL

 

 

 

 

 

2

 

(Qty. Per Unit)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FILTERS

QUANTITY PER UNIT (12" X 24" X 2"

 

 

 

12

 

TOTAL FACE AREA (Sq. Ft.)

 

 

 

24

 

 

 

 

 

 

CHARGE

REFRIGERANT

 

SYSTEM No.1

 

23/0

24/0

 

23/8

23/8

22 (Lb./Oz.)

 

SYSTEM No. 2

 

23/8

24/0

 

23/8

23/8

 

 

 

 

 

 

 

COOLING ONLY

 

2260

2540

 

2560

2660

 

BASIC UNIT

 

GAS / ELECTRIC

 

N24

2460

2740

 

2760

2860

 

 

 

 

N32

2500

2780

 

2800

2900

 

 

 

 

 

 

 

 

 

DOUBLE WALL

 

 

 

 

260

 

 

 

 

ECONOMIZER

 

 

 

160

 

 

 

 

ECONOMIZER WITH

 

 

 

245

 

 

 

 

POWER EXHAUST

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOTORIZED DAMPER

 

 

 

150

 

 

OPTIONS

 

 

 

18 KW

 

 

25

 

OPERATING

 

 

ELECTRIC HEATER

 

36 KW

 

 

30

 

WEIGHTS

 

 

 

54 KW

 

 

35

 

 

 

 

 

 

 

 

(LBS.)

 

 

 

 

 

 

 

 

 

 

 

 

 

72 KW

 

 

40

 

 

 

 

HOT GAS BYPASS

 

 

 

 

10

 

 

 

 

SUPPLY FAN VFD

 

 

See Table 23

 

 

ACCESSORIES

 

ROOF CURB

 

 

 

185

 

 

 

 

BAROMETRIC DAMPER

 

 

 

45

 

 

 

 

ECONOMIZER / MOTORIZED

 

 

 

55

 

 

 

 

DAMPER RAIN HOOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ECONOMIZER / POWER

 

 

 

90

 

 

 

 

EXHAUST RAIN HOOD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

WOOD SKID

 

 

 

220

 

28

Johnson Controls Unitary Products

Page 28
Image 28