Johnson Controls J15 warranty SOUND POWER RATING1, Capacity Ratings - Ari, Gas Heat Ratiings

Models: J15

1 40
Download 40 pages 44.97 Kb
Page 9
Image 9
TABLE 1: SOUND POWER RATING1

349687-JTG-A-1007

TABLE 1: SOUND POWER RATING1

 

 

ESP

BLOWER

 

 

 

SOUND POWER (db 10-12

Watts)

 

 

 

UNIT

 

 

 

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

Octave Band Centerline Frequency (Hz)

 

SWL

dB(A)

SIZE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

@

 

 

IWG

RPM

BHP

63

125

250

500

1,000

2,000

 

4,000

8,000

dB(A)

 

 

 

10Ft.2

 

 

 

 

J15DJ

6,000

1.00

1,080

4.60

99

99

89

82

84

77

 

72

67

89

56

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J18, 20 DJ

8,000

1.00

1,120

6.65

102

102

92

85

87

80

 

75

70

92

59

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J25DJ

10,000

1.30

1160

12.5

108

108

98

91

93

86

 

81

76

98

65

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way of knowing the details of each system. This constitutes and expectation to any specification or guaran- tee requiring a dBA value or sound data in any other form than sound power level ratings.

2.At a distance of 10 feet from the blower.

TABLE 2: CAPACITY RATINGS - (ARI 360)1

MODEL

MBH

EER2

IPLV3

COOLING ONLY

 

 

 

J15DJC/E00

178

12.0

12.5

J18DJC/E00

208

11.7

12.7

J20DJC/E00

230

11.3

12.0

J25DJC/E00

292

10.5

11.2

COOLING WITH GAS HEAT

 

 

 

J15DJN/S

178

12.0

12.5

J18DJN/S

208

11.7

12.7

J20DJN/S

230

11.3

12.0

J25DJN/S

292

10.5

11.2

COOLING WITH ELECTRIC HEAT

 

 

J15DJE18

178

12.0

12.5

J15DJE36

178

12.0

12.5

J15DJE54

176

11.8

12.2

J15DJE72

176

11.8

12.2

J18DJE18

208

11.7

12.7

J18DJE36

208

11.7

12.7

J18DJE54

206

11.5

12.4

J18DJE72

206

11.5

12.4

J20DJE18

230

11.3

12.0

J20DJE36

230

11.3

12.0

J20DJE54

228

11.1

11.7

J20DJE72

228

11.1

11.7

J25DJE18

292

10.5

11.2

J25DJE36

292

10.5

11.2

J25DJE54

290

10.3

11.0

J25DJE72

290

10.3

11.0

1.Certified in accordance with the Unitary Large Equip- ment certification program which is based on ARI Stan- dard 340/360.

2.EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (Btuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).

3.IPLV = Integrated Part Load Value.

TABLE 3: GAS HEAT RATIINGS

MODEL

MBH INPUT

MBH OUTPUT

J15DJN/S24

300

240

 

 

 

J15DJN/S32

400

320

J18DJN/S24

300

240

 

 

 

J18DJN/S32

400

320

J20DJN/S24

300

240

 

 

 

J20DJN/S32

400

320

J25DJN/S24

300

240

 

 

 

J25DJN/S32

400

320

NOTE: All gas units are two-stage heating. First stage is 50% of total.

S.S.E. = Steady State Efficiency (80%) - output divided by input.

For units with VFD and electric or gas heat, the speed of the indoor blower motor continues to be controlled by duct static pressure via the VAV control board.

If there are VAV boxes present in the duct sys- tem, the boxes must be driven to the full-open position using a customer-supplied power source to assure adequate airflow across elec- tric heating elements or gas heat exchanger tubes.

Johnson Controls Unitary Products

9

Page 9
Image 9
Johnson Controls J15 warranty SOUND POWER RATING1, Capacity Ratings - Ari, Gas Heat Ratiings