349687-JTG-A-1007

TABLE 15: SUPPLY AIR BLOWER PERFORMANCE (25 TON) - GAS HEAT 300 MBH - BOTTOM DUCT CONNECTIONS

BLOWER

MOTOR

 

 

 

 

 

 

 

 

 

CFM

 

 

 

 

 

 

 

PULLEY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SPEED,

 

 

7500

 

 

 

8750

 

 

10000

 

 

11250

 

 

12500

 

(TURNS

 

 

 

 

 

 

 

 

 

 

 

 

(RPM)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OPEN)*

ESP

 

BHP

 

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

ESP

BHP

KW

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208 VOLT AND STANDARD DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

975

6.0

1.2

 

5.9

 

4.9

5.0

7.3

6.0

-

-

-

-

-

-

-

-

-

1005

5.0

1.4

 

6.2

 

5.1

0.7

7.7

6.3

-

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1040

4.0

1.6

 

6.6

 

5.4

0.9

8.1

6.7

0.2

9.7

8.0

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1070

3.0

1.8

 

6.9

 

5.7

1.1

8.5

7.0

0.4

10.2

8.3

-

-

-

-

-

-

1100

2.0

2.0

 

7.3

 

6.0

1.3

8.9

7.3

0.6

10.6

8.7

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1135

1.0

2.2

 

7.7

 

6.3

1.6

9.3

7.6

0.8

11.1

9.1

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1165

0.0

2.4

 

8.0

 

6.6

1.8

9.7

8.0

1.0

11.6

9.5

0.2

13.5

11.0

-

-

-

208 VOLT AND HIGH STATIC DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

1140

6.0

2.2

 

7.7

 

6.3

1.6

9.4

7.7

0.9

11.2

9.2

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1180

5.0

2.5

 

8.2

 

6.7

1.9

9.9

8.1

1.2

11.8

9.7

0.3

13.7

11.2

-

-

-

1215

4.0

2.7

 

8.6

 

7.0

2.1

10.4

8.5

1.4

12.3

10.1

0.6

14.3

11.7

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1255

3.0

3.0

 

9.1

 

7.4

2.4

11.0

9.0

1.7

12.9

10.6

0.9

15.0

12.3

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1290

2.0

3.2

 

9.5

 

7.8

2.7

11.5

9.4

2.0

13.5

11.1

1.2

15.6

12.8

-

-

-

1330

1.0

3.5

 

10.0

 

8.2

3.0

12.0

9.9

2.3

14.1

11.6

1.5

16.4

13.4

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1365

0.0

3.7

 

10.5

 

8.6

3.2

12.6

10.3

2.6

14.7

12.1

1.8

17.0

13.9

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230/460/575

VOLT AND

STANDARD

DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

975

6.0*

1.4

 

5.9

 

4.9

1.0

7.3

6.0

0.5

8.8

7.2

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1005

5.0

1.6

 

6.2

 

5.1

1.2

7.7

6.3

0.7

9.2

7.6

0.1

10.9

8.9

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1040

4.0

1.8

 

6.6

 

5.4

1.4

8.1

6.7

0.9

9.7

8.0

0.3

11.4

9.4

-

-

-

1070

3.0

2.0

 

6.9

 

5.7

1.6

8.5

7.0

1.1

10.2

8.3

0.6

11.9

9.8

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1100

2.0

2.1

 

7.3

 

6.0

1.8

8.9

7.3

1.3

10.6

8.7

0.8

12.4

10.2

0.2

14.3

11.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1135

1.0

2.4

 

7.7

 

6.3

2.0

9.3

7.6

1.6

11.1

9.1

1.0

13.0

10.6

0.4

14.9

12.2

1165

0.0

2.6

 

8.0

 

6.6

2.2

9.7

8.0

1.8

11.6

9.5

1.3

13.5

11.0

0.7

15.5

12.7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

230/460/575

VOLT AND

HIGH STATIC DRIVE

 

 

 

 

 

 

 

 

 

 

 

 

 

1140

6.0

2.4

 

7.7

 

6.3

2.1

9.4

7.7

1.6

11.2

9.2

1.1

13.1

10.7

0.5

15.0

12.3

1180

5.0

2.7

 

8.2

 

6.7

2.3

9.9

8.1

1.9

11.8

9.7

1.4

13.7

11.2

0.8

15.8

12.9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1215

4.0

2.9

 

8.6

 

7.0

2.6

10.4

8.5

2.2

12.3

10.1

1.7

14.3

11.7

1.1

16.4

13.5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1255

3.0

3.2

 

9.1

 

7.4

2.9

11.0

9.0

2.5

12.9

10.6

2.0

15.0

12.3

1.4

17.2

14.1

1290

2.0

3.4

 

9.5

 

7.8

3.1

11.5

9.4

2.7

13.5

11.1

2.2

15.6

12.8

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1330

1.0

3.7

 

10.0

 

8.2

3.4

12.0

9.9

3.0

14.1

11.6

2.6

16.4

13.4

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1365

0.0

3.9

 

10.5

 

8.6

3.7

12.6

10.3

3.3

14.7

12.1

2.9

17.0

13.9

-

-

-

NOTES: 1.Blower performance includes a gas-fired heat exchanger, fixed outdoor air, two-inch T/A filters and a dry evaporator coil. 2.Refer to the additional Static Resistances table.

ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.

*Do NOT close the pulley below 1 turn open.

**Factory setting.