Units equipped with VFD’s shall have
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the
REFRIGERANT COMPONENTS
Compressors:
a.Shall be Scroll compressors internally protected with internal
b.Shall have internal spring isolation and sound muf- fling to minimize vibration and noise, and be exter- nally isolated on a dedicated, independent mounting.
Coils:
a.Evaporator and condenser coils shall have alumi- num plate fins mechanically bonded to seamless internally enhanced copper tubes with all joints brazed. Special Phenolic coating shall be available as a factory option.
b.Evaporator and Condenser coils shall be of the direct expansion,
Refrigerant Circuit and Refrigerant Safety Components shall include:
a.
b.Filter drier/strainer to eliminate any moisture or for- eign matter.
c.Accessible service gage connections on both suc- tion and discharge lines to charge, evacuate, and measure refrigerant pressure during any necessary servicing or troubleshooting, without losing charge.
d.The refrigeration system shall provide at least 15° F of
e.All models shall have two independent circuits.
f.Hot gas bypass option shall be
UNIT CONTROLS
a.Unit shall be complete with
b.Unit shall incorporate a lockout circuit which pro- vides reset capability at the space thermostat or base unit, should any of the following standard safety devices trip and shut off compressor.
c.
1.
2.
d.Unit shall incorporate "AUTO RESET" compressor over temperature, over current protection.
e.Unit shall operate with conventional thermostat designs and have a low voltage terminal strip for easy
f.Unit control board shall have
g.Standard controls shall include
h.Control board shall monitor each refrigerant safety switch independently.
i.Control board shall retain last 5 fault codes in non volatile memory, which will not be lost in the event of a power loss.
GAS HEATING SECTION (J**DJN MODELS)
Shall be designed with induced draft combustion with post purge logic and energy saving direct spark ignition, redun- dant main gas valve. Ventor wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of
38 | Johnson Controls Unitary Products |