TABLE 13: SUPPLY AIR BLOWER PERFORMANCE (17.5 TON) - GAS HEAT 210 MBH - BOTTOM DUCT CONNECTIONS
BLOWER | MOTOR |
|
|
|
|
|
| CFM |
|
|
|
|
| |
PULLEY |
|
|
|
|
|
|
|
|
|
|
|
|
| |
SPEED, |
| 6000 |
|
| 7000 |
|
|
| 8000 |
|
| 9000 |
| |
(TURNS |
|
|
|
|
|
|
|
|
| |||||
(RPM) |
|
|
|
|
|
|
|
|
|
|
|
|
| |
OPEN)* | ESP | BHP | KW | ESP | BHP | KW |
| ESP | BHP | KW | ESP | BHP | KW | |
|
| |||||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
208 VOLT AND | STANDARD | DRIVE |
|
|
|
|
|
|
|
|
|
|
|
|
870 | 6.0** | 1.3 | 3.6 | 3.0 | 0.7 | 4.3 | 3.7 |
| 0.2 | 5.1 | 4.3 | - | - | - |
900 | 5.0 | 1.4 | 3.8 | 3.2 | 0.9 | 4.7 | 4.0 |
| 0.4 | 5.6 | 4.7 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
930 | 4.0 | 1.6 | 4.1 | 3.4 | 1.1 | 5.0 | 4.2 |
| 0.6 | 5.9 | 5.0 | 0.1 | 6.7 | 5.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
950 | 3.0 | 1.7 | 4.2 | 3.6 | 1.3 | 5.1 | 4.3 |
| 0.8 | 6.0 | 5.1 | 0.2 | 6.9 | 5.8 |
980 | 2.0 | 1.9 | 4.5 | 3.8 | 1.5 | 5.4 | 4.5 |
| 1.0 | 6.3 | 5.3 | 0.4 | 7.2 | 6.1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
995 | 1.5 | 2.1 | 4.6 | 3.9 | 1.6 | 5.5 | 4.7 |
| 1.1 | 6.4 | 5.4 | 0.5 | 7.5 | 6.3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1015 | 1.0 | 2.2 | 4.8 | 4.0 | 1.7 | 4.7 | 4.8 |
| 1.2 | 6.6 | 5.6 | 0.7 | 7.8 | 6.6 |
208 VOLT AND | HIGH STATIC | DRIVE |
|
|
|
|
|
|
|
|
|
|
|
|
950 | 6.0 | 1.7 | 4.2 | 3.6 | 1.3 | 5.1 | 4.3 |
| 0.8 | 6.0 | 5.1 | 0.2 | 6.9 | 5.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
980 | 5.0 | 1.9 | 4.5 | 3.8 | 1.5 | 5.4 | 4.5 |
| 1.0 | 6.3 | 5.3 | 0.4 | 7.2 | 6.1 |
995 | 4.5 | 2.1 | 4.5 | 3.9 | 1.6 | 5.5 | 4.7 |
| 1.1 | 6.4 | 5.4 | 0.5 | 7.5 | 6.3 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1025 | 3.5 | 2.3 | 4.9 | 4.1 | 1.8 | 5.8 | 4.9 |
| 1.3 | 6.7 | 5.7 | 0.7 | 8.0 | 6.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1050 | 2.5 | 2.5 | 5.1 | 4.3 | 2.0 | 6.1 | 5.1 |
| 1.4 | 7.1 | 6.0 | 0.9 | 8.4 | 7.0 |
1065 | 2.0 | 2.6 | 5.3 | 4.4 | 2.1 | 6.3 | 5.3 |
| 1.5 | 7.3 | 6.2 | 1.0 | 8.6 | 7.2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1100 | 1.0 | 2.9 | 5.6 | 4.7 | 2.3 | 6.8 | 5.7 |
| 1.8 | 7.9 | 6.6 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
230/460/575 VOLT AND STANDARD DRIVE |
|
|
|
|
|
|
|
|
|
|
| |||
870 | 6.0** | 1.3 | 3.6 | 3.0 | 0.7 | 4.3 | 3.7 |
| 0.2 | 5.1 | 4.3 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
900 | 5.0 | 1.4 | 3.8 | 3.2 | 0.9 | 4.7 | 4.0 |
| 0.4 | 5.6 | 4.7 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
930 | 4.0 | 1.6 | 4.1 | 3.4 | 1.1 | 5.0 | 4.2 |
| 0.6 | 5.9 | 5.0 | 0.1 | 6.7 | 5.7 |
950 | 3.5 | 1.7 | 4.2 | 3.6 | 1.3 | 5.1 | 4.3 |
| 0.8 | 6.0 | 5.1 | 0.2 | 6.9 | 5.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
965 | 2.5 | 1.9 | 4.5 | 3.8 | 1.5 | 5.4 | 4.5 |
| 1.0 | 6.3 | 5.3 | 0.4 | 7.2 | 6.1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
995 | 2.0 | 2.1 | 4.6 | 3.9 | 1.6 | 5.5 | 4.7 |
| 1.1 | 6.4 | 5.4 | 0.5 | 7.5 | 6.3 |
1015 | 1.5 | 2.2 | 4.8 | 4.0 | 1.7 | 5.7 | 4.8 |
| 1.2 | 6.6 | 5.6 | 0.6 | 7.8 | 6.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1025 | 1.0 | 2.3 | 4.9 | 4.1 | 1.8 | 5.8 | 4.9 |
| 1.3 | 6.7 | 5.7 | 0.7 | 8.0 | 6.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
230/460/575 VOLT AND HIGH STATIC DRIVE |
|
|
|
|
|
|
|
|
|
|
| |||
950 | 6.0 | 1.7 | 4.2 | 3.6 | 1.3 | 5.1 | 4.3 |
| 0.8 | 6.0 | 5.1 | 0.2 | 6.9 | 5.8 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
980 | 5.0 | 1.9 | 4.5 | 3.8 | 1.5 | 5.4 | 4.5 |
| 1.0 | 6.3 | 5.3 | 0.4 | 7.2 | 6.1 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
995 | 4.5 | 2.1 | 4.6 | 3.9 | 1.6 | 5.5 | 4.7 |
| 1.1 | 6.4 | 5.4 | 0.5 | 7.5 | 6.3 |
1015 | 4.0 | 2.2 | 4.8 | 4.0 | 1.7 | 5.7 | 4.8 |
| 1.2 | 6.6 | 5.6 | 0.6 | 7.8 | 6.6 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1025 | 3.5 | 2.3 | 4.9 | 4.1 | 1.8 | 5.8 | 4.9 |
| 1.3 | 6.7 | 5.7 | 0.7 | 8.0 | 6.7 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1050 | 3.0 | 2.5 | 5.1 | 4.3 | 2.0 | 6.1 | 5.1 |
| 1.4 | 7.1 | 6.0 | 0.9 | 8.4 | 7.0 |
1065 | 2.5 | 2.6 | 5.3 | 4.4 | 2.1 | 6.3 | 5.3 |
| 1.5 | 7.3 | 6.2 | 1.0 | 8.6 | 7.2 |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1100 | 1.5 | 2.9 | 5.6 | 4.7 | 2.3 | 6.8 | 4.7 |
| 1.8 | 7.9 | 6.6 | - | - | - |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1120 | 1.0 | 3.1 | 5.8 | 4.9 | 2.5 | 7.0 | 5.9 |
| 1.9 | 8.3 | 6.9 | - | - | - |
NOTES: 1.Blower performance includes a
ESP = External Static Pressure available for the supply and return air duct system. All internal unit resistances have been deducted from the total static pressure of the blower.
*Do NOT close the pulley below 1 turn open.
**Factory setting.
20 | Johnson Controls Unitary Products |