Johnson Controls TM9X*MP UIM-B-01211, Air Supply Openings and Ducts, Ventilated Combustion Air

Models: TM9X*MP

1 38
Download 38 pages 44.62 Kb
Page 27
Image 27
Air Supply Openings and Ducts

697936-UIM-B-01211

 

 

Gas

Gable

 

Vent

Vent

Ventilated

 

 

 

Optional

Attic

 

Top Above

 

Inlet (a)

 

Insulation

 

 

 

Soffit

Outlet

 

Vent

Air (a)

rnaceuF

 

Gas

 

 

 

Water

 

 

Heater

 

 

Ventilated

 

 

Crawl Space

 

 

 

Gas

 

 

 

 

Gable

Vent

 

 

 

 

 

 

 

 

 

Vent

 

 

 

 

 

Ventilated

 

 

 

 

 

Attic

 

 

 

 

 

Top Above

 

 

 

 

 

Insulation

 

 

 

 

Soffit

 

 

 

Outlet

 

Vent

 

 

 

 

 

 

 

Air (b)

 

 

 

 

 

 

 

Heater

Furnace

Inlet

Inlet

Heater

 

Gas

 

 

 

Gas

Inlet

Water

 

 

 

Water

 

 

 

 

 

Air (b)

 

 

Air (a)

Air (b)

 

Gas

Vent

 

Outlet

 

Air (a)

Furnace

Inlet

 

 

Air (a)

FIGURE 36: Outside and Ambient Combustion Air

Air Supply Openings and Ducts

1.An opening may be used in lieu of a duct to provide to provide the outside air supply to an appliance unless otherwise permitted by the authority having jurisdiction. The opening shall be located within 12” (30.5 cm) horizontally from, the burner level of the appliance. Refer to “AIR SOURCE FROM OUTDOORS AND VENT AND SUPPLY AIR SAFETY CHECK” in these instructions for additional information and safety check procedure.

2.The duct shall be either metal, or a material meeting the class 1 requirements of CAN4-S110 Standard for Air Ducts.

3.The duct shall be least the same cross-sectional area as the free area of the air supply inlet opening to which it connects.

4.The duct shall terminate within 12” (30.5 cm) above, and within 24” (61 cm) horizontally from, the burner level of the appliance having the largest input.

5.A square or rectangular shaped duct shall only be used when the required free area of the supply opening is 9 in2 (58.06 cm2) or larger. When a square or rectangular duct is used, its small dimen- sion shall not be less than 3” (7.6 cm).

6.An air inlet supply from outdoors shall be equipped with a means to prevent the direct entry of rain and wind. Such means shall not reduce the required free area of the air supply opening.

7.An air supply inlet opening from the outdoors shall be located not less than 12” (30.5 cm) above the outside grade level.

Combustion Air Source from Outdoors

1.Two permanent openings, one within 12” (30.5 cm) of the top and one within 12” (30.5 cm) of bottom of the confined space, Two per- manent openings, shall communicate directly or by means of ducts with the outdoors, crawl spaces or attic spaces.

2.One permanent openings, commencing within 12” (30.5 cm) of the top of the enclosure shall be permitted where the equipment has clearances of at least 1” (2.54 cm) from the sides and back and 6” (15.2 cm) from the front of the appliance. The opening shall com- municate directly with the outdoors and shall have a minimum free area of:

a.1 square inch per 3000 BTU per hour (322 cm2 per 0.879 kW) of the total input rating of all equipment located in the enclosure.

b.Not less than the sum of all vent connectors in the confined space.

3.The duct shall be least the same cross-sectional area as the free area of the air supply inlet opening to which it connects.

4.The blocking effects of louvers, grilles and screens must be given consideration in calculating free area. If the free area of a specific louver or grille is not known. Refer to Table 11.

Ventilated Combustion Air

The ventilated attic space or a crawl space from which the combustion air is taken must comply with the requirements specified in “AIR SOURCE FROM OUTDOORS” in this instruction or in Section 5.3, Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 (latest edition). This type installation requires two properly sized pipes. One brings combustion air from a properly ventilated attic space or crawl space and a second pipe that extends from the furnace vent connection (top right of unit) to the exterior of the building. Refer to Table 7 for intake pipe sizing, allowable length and elbow usage. Follow all notes, procedures and required materials in the "COMBUSTION AIR/VENT PIPE SIZING" section in these instructions when installing the combustion air pipe from the unit and into a ventilated attic space or crawl space. DO NOT terminate vent pipe in an Attic or Crawl Space.

Ventilated Combustion Air Termination

Refer to Figure 36 for required attic termination for the combustion air intake pipe. For attic termination, use two 90 elbows with the open end in a downward position. Be sure to maintain 12” (30.5 cm) clearance above any insulation, flooring or other material.

A crawl space combustion air installation consists of a straight pipe from the PVC coupling on the burner box that extends into the crawl space and terminates with a 1/4” (6.4 mm) mesh screen and no elbows.

Johnson Controls Unitary Products

27

Page 27
Image 27
Johnson Controls TM9X*MP UIM-B-01211, Air Supply Openings and Ducts, Combustion Air Source from Outdoors