Johnson Controls TM9X*MP installation manual UIM-B-01211, Condensate Drain Termination

Models: TM9X*MP

1 38
Download 38 pages 44.62 Kb
Page 16
Image 16
FIGURE 21: Typical. Combustion Pipe Drain Tee

697936-UIM-B-01211

CONDENSATE DRAIN TERMINATION Exhaust Pipe

Manual backgroundCombustion Air Pipe

Manual background Tee with Drain Trap

Manual backgroundTrap

Manual background Connect to Drain

FIGURE 21: Typical. Combustion Pipe Drain Tee

CONDENSATE DRAIN TERMINATION

A condensate sump pump MUST be used if required by local codes, or if no indoor floor drain is available. The condensate sump pump must be approved for use with acidic condensate.

DO NOT terminate the condensate drain in a chimney, or where the drain line may freeze. If the drain line will be exposed to temperatures below freezing, adequate measures must be taken to prevent the drain line from freezing. Failure to provide proper protection from freezing can result in improper operation or damage to the equipment and possible property damage. When exposed to temperatures below freezing, use of a 3 to 6 watt per foot at 115 VAC, 40°F (4.4°C) self-regulating, shielded and waterproof heat tape is recommended on the drain line outside the furnace.

DO NOT trap the drain line at any other location than at the conden- sate drain trap supplied with the furnace.

Liquid anti-freeze will cause damage to internal plastic parts of this furnace. DO NOT attempt to winterize the furnace using liquid anti-freeze.

16

Johnson Controls Unitary Products

Page 16
Image 16
Johnson Controls TM9X*MP installation manual UIM-B-01211, Condensate Drain Termination, Typical. Combustion Pipe Drain Tee