1. Measure height of the chimney to fireplace

Listed Direct Vent Termination Cap

Venting InstallationThrough a Prefabricated Fireplace

 

 

1. Measure height of the chimney to fireplace

 

 

opening. Determine if both the intake and

 

 

exhaust will be extended to the top of the

 

 

chimney.

Factory-built Listed

2. Cut the appropriate lengths of flex for both the

Gas Chimney

 

intake and exhaust.

 

 

3. Attach the appropriate ends of the flex to the

 

 

chimney termination kit.

 

PIPE

4. Drop the liners down the chimney from the top

 

and rest the termination kit atop the chimney.

 

FLEX

 

5. Seal the chimney termination kit to the top of the

 

INTAKE

 

chimney pipe with high temperature sealant.

 

 

 

AIR

6. Secure the appropriate DIRECT VENT CAP to the

Listed Flexible

termination kit.

 

7. Inside the fireplace, fully extend the flex and cut

Gas Liners

 

Max. Height 35 ft.

PIPE

off the excess flex so that the liners hang ap-

Min. Height 10ft.

proximately 15” from the floor of the fireplace.

FLEX

 

8. If the intake flex is not attached to the chimney

 

EXHAUST

termination kit: See NOTICE on page 12.

 

 

 

 

A. It is now necessary to install a minimum of a 6

 

 

foot length of flex into the flue for the intake air.

INTAKE FLEX MUST

 

B. A METAL damper block off plate must be

EXTEND A MINIMUM

 

 

constructed and installed in the damper area to

OF 6’ AND INTO

 

THE CHIMNEY PIPE

 

completely seal off the flue from the room.

 

 

Remember to cut holes for both the intake and

Maintain proper

 

exhaust liners in the block off plate.

clearance to Mantel

 

C. A direct vent cap is still required to allow fresh

and Trim

 

 

 

air into the chimney flue and ultimately into the

Metal block-off plate is

 

intake flex and insert.

required to seal flue

 

D. Attach the Fireplace Conversion Notice to the

from the living area if

 

back of the fireplace if appropriate.

Air Intake pipe does not

 

 

 

connect directly to a

 

9. Compress the liners so that they are hanging

Direct Vent Termination

 

above the height of the fireplace opening and are

at the top of the

 

chimney

 

out of the way.

 

To Exhaust

10. Position the insert without surround panels

Attach Fireplace

Collar

half-way inside the fireplace and attach the liners

 

to the appropriate ports on the rear of the stove.

Conversion Notice

 

Be sure not to cross vent the insert.

Plate to Rear Wall

To Air

of Fireplaceif the

Intake

11. Secure the liners to the ports using sheet metal

damper has been

Collar

modified.

 

screws or hose clamps. No silicone or sealant is

Figure 8. Factory-built Fireplace Vent42345678901Configuration.

required.

 

23234

 

 