Kenmore 153.330751 Installation Instru ti6hs ontd, Venting contd, A Warning, Awarningi

Models: 153.3304OI 153.330551 153.330451 153.330751 153.330701 153.330501

1 28
Download 28 pages 33.66 Kb
Page 14
Image 14
Installation Instru ti6hs ( ont'd)

Installation Instru ti6hs ( ont'd)

Venting (cont'd)

All vent gases must be completely vented to the outdoors of the structure (dwelling). Installonly the draft hood provided with the new water heater and no other drafthood.

Ven_ pipes must be secured at each ioint with sheet metal screws,

TO

CHIMNEY

RISE PER LINEAR

FOOT

II

VENT PIPE INSTALLATION

There must be a minimum of 6" clearance between single wall vent pipe and any combustible material. Fill and seal any clear-

ance between single wall vent pipe and combustible material with mortar mix, cement, or other noncombustible substance.

Fot other than single wall, follow vent pipe manufacturer's clear- ance specifications. To insure a tight fit of the vent pipe in a brick chimney, seal around the vent pipe with mortar mix cement.

I

. A WARNING

 

J

 

Failureto have reqmred _

between vent pipingand

 

 

combustiblematerialwill resultin a flr_ hazard,

I

A WARNINGI I Besurevantplpob properlyconnectod pr_mt escapeofI [ den_rous _ gesoswitch €ouldcamedeadtyasphyxiatio_

Gas

AWARNING

take sure the gas suppliedis the same type listed on the nodel rating plate. The inlet gaspeessummust not exceed

0.5in.water column(2.61dPa)for natural gasor 13 in.wa_er column (3.2kPa) for propane (L.R) ga_ The minimum inlet gas pressurelistedon the model radng plate isfor the pur- poseof input

AWARNING

.

I

[ ff the gascontrol valveissol.-tedto pressuresexceeding 'AI I poundper squareinch(3.SkPa),the damageto the gascon-J

I trel valve €°uld result in a tire oc _

ion fr°m leak_g ges" J

I. A WARNING

If the main gashne shutoffserving.ai.gasappliancesIis used, aisotorn "OFF" the ps at eachapld*anceLeme. all gesappli-

ancesshut off untilthe water heater installationiscomplete.

A gas line of sufficient size must be run to the water heater. Consult the latest edition of National Fuel Gas Code ANSI

Z223.1, also referred to as NFPA 54 and the gas company con- cerning pipe size.

There must be:

A readilyaccessible manual shut off valve in the gas supply line serving the water heater, and

A drip leg (sediment trap) ahead of the gas control valve to help,

prevent dirt and foreign materials from enteting the gas enntroi valve.

A flexible gas connector or a ground joint union between the shutoffvalve and control valve to permit servicing of the unit.

i

A WARNING

Be sure to check all the gas piping for leaks before lighting the water heater. Use a soapy water solution, not a march or open throe. Rinse offsoapy solution and wipe dry.

Chemical vapor corrosionof the flue and vent system may occurif air for combustioncontainscertain chemicalvapors.

Spray .canpropellantg cleaningsolvents, refrigerator and air

conditioner refrigerants,swimming pool chemicals,.calcium and sodiumchloride,waxes,bleach,and processthem,cals are

typical compoundswhichare potentiallycorrosive.

Standard Models are for installation up to 3,300 feet above sea level.

fI-_h Altitude Models are for installation from 3,300 to 5,500

tabove sea level.

Ifa standard model is installed above 3,300 feet or a high altitude model is installed above 5,500 feet, the input taring must he reduced at the rate of 4 percent for each 1,000 feet above sea level.

Contact your local Sears Service Center or gas utility for further information.

The appliance and its gasconnection must be leak tested

AWARNINGI

beforeplacingthe appliance in operation.

14

Page 14
Image 14