Kenmore 153.330701, 153.330451 Installation InstrudionS C6ntd, Combustion Air and Ventilation

Models: 153.3304OI 153.330551 153.330451 153.330751 153.330701 153.330501

1 28
Download 28 pages 33.66 Kb
Page 10
Image 10
Installation InstrudionS (C6nt'd)

Installation InstrudionS (C6nt'd)

Combustion Air and Ventilation

for Appliances Located in Unconfined Spaces

Unconfined Space is a space whose volume is not less than 50 cubic feet per 1,000 Btu per hour of the aggregate input ratine:

of all appliances installed in that space. Roo--ms-comm'unicatin_ directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a

,partof the unconfined space

m unconfined spaces in buildings, infiltration may be adequate to provide air for combustion, ventilation and dilution of flue

gases. However, in buildings of tight construction (for example, weather stripping, heavily insulated, caulked, vapor barrier, etc.), additional air ma_ need to be provided using the methods described in Combustion Air and Ventilation for Appliances Located in Confined Spaces, b.

1.When directly communicating with the outdoors, each open-

in,shall have a minimum free area of 1 square inch per 4,000 BI u per hour of total input rating of all equipment in the enclosure. (See Figure 3.)

2.When communicating with the outdoors through vertical

ducts, each opening shall have a minimum free area of 1

s_uare inch per 4,000 BTU per hour of total input rating of all equipment in the enclosure. (See Figure 4.)

CHIMNEy OR _ VEnT

VEhrrUT_O_ LOU_

(each _ oJ a._: I

Combustion Air and Ventilation for Appliances Located in

Confined Spaces

Confined Space is a space whose volume is less than 50 cubic feet per 1,000 Btu per hour of the aggregate input rating of all

appliances installed in that space.

.

-

ALL AIR FROM INSIDE BUILDINGS.

 

 

(See Page 9 Figure 1, and Figure2 below)

The confined space shall be provided with two permanent

oi_enin_s communicating directly with an additional room(s) or suttlcient volume so that the combined volume of all

spaces meets the criteria for an unconfined space. The total input of all gas utilization equipment installed in the com- bined space shall be considered in making this determination.

Each opening shall have a minimum free area of one square inch per 1,000 BTU per hour of the total input rating of all _s utilization equipment in the confined space, but not less an 100 square inches. One opening shall commence within

12" of the top and one commencing within 12" of the bot- tom of the enclosure.

b. ALL AIR FROM OUTDOORS: (see Figures 3-5)

The confined space shall be provided with two permanent openings, one commencing within 12 of the top and one commenc'ng within 12' from the bottom of the endosure.

The openings shall communicate directly, or by ducts, with

the outdoors or spaces (crawl or attic) that freely communi- care with the outdoors.

Figure 3 ]

AIR OUTLET

WA'tER _ATE_

I_T AIR DUCT

Figure 4 ]

3.When communicating with the outdoors through horizontal

ducts, each opening shall have a minimum free area of 1

_uare inch per 2,000 BTU per hour of total input rating of equipment in the enclosure. (See Figure 5.)

_i_caM_v

on C,AS _Nr

4.When ducts are used, they shall be of the same cross-sectional area as the free area of the openings to which they connect. The minimum short side dimension of rectangular air ducts shall not be less than 3". (See Figure 5.)

. Louvers and Grilles: In calculating free area, consideration

shall be given to the blocking effect of louvers, grilles or screens protecting openings. Screens used shall not be smaller

than _"mesh. If the free area through a design of louver or grille is known, it should be used in calculating the size open- ing required to provide the free area specified. If the design and free area is not known, it may be assumed that wood lou- vers will be 20-25 percent free area and metal louvers and

grilles will have 60-75percent free area. Louvers and grilles shall be fixed in the open position or interlocked with the

equipment so that they are opened automatically during equipment operation.

6.Special Conditions Created by Mechanical Exhausting or

Fireplaces: Operation of exhaust fans, ventilation systems, domes dryers or fireplaces may create conditions requiring

special attention to avoid unsatisfactory operation of installed

10gas utilization equipment.

Page 10
Image 10
Kenmore 153.330701, 153.330451, 153.330501 Installation InstrudionS C6ntd, Combustion Air and Ventilation, Confined Spaces