Kenmore 153.33298 Installation Instructions contd, Venting contd, I I Groundorsnow, inside bldg

Models: 153.332960HA 153.33298 153.332890HA 153.332990HA 153.33296 153.33288 153.332861 153.332870HA

1 44
Download 44 pages 39.07 Kb
Page 20
Image 20
I I GROUNDORSNOW

Installation Instructions (cont'd)

Venting (cont'd)

VENTING THROUGH AN OUTSIDE WALL WITH

LOW GROUND CLEARANCE

1.When the vent piping cannot pass through an outside wall at a height greater than or equal to 12" above the ground (or above snow accumulation level), then the installation can be modified as shown below.

/,%

[//_,

/%

7[

MIN. ABOVE

>:_

I I GROUNDORSNOW

_

ACCiNULATION LEVEL

2.Refer to the tables below for maximum vent lengths for low ground clearance installations. All installations assume the use

of two additional 90 ° elbows and the standard 45 ° vent cap with screen outside of the exterior wall.

ALL MODELS -- LOW GROUND CLEARANCE

3" DIA.VENT

NUMBER OF 90 ° DEG.

MAX. LENGTH (FT.) ELBOWS* (inside bldg)

105I

1002

953

904

855

8O6

ALL MODELS -- LOW GROUND CLEARANCE

OPTIONAL 2" VENT PIPING

2" DIA.VENT

NUMBER

OF 90 ° DEG.

MAX. LENGTH (FT.)

ELBOWS*

(inside bldg)

4O

 

I

35

 

2

3O

 

3

25

 

4

2O

 

5

15

 

6

CEMENTING PVC, ABS OR CPVC PIPE AND

FITTINGS

Read and observe all safety information printed on primer, cleaner, and cement containers.

_. DANGERI Primer, cleaner, and cements are extremely I flammable. They are harmful or fatal if swallowed. The I vapors are harmful. They may irritate eyes and skin

and can be absorbed through the sk n.

_. PRECAUTIONS

Always store primers, cleaner, and cements in cool, dry, well ventilated places. Do not store them near

heat, sparks, or flames. Keep containers closed. Use them in well ventilated areas. Wear impervious cloth- ing while handling. Do not smoke, eat, or drink while handling. Wash thoroughly after handling and before eating. Wear eye protection when handling. If swal- lowed, drink water, do not induce vomiting, and call a physician or poison control center immediately. If inhaled, get fresh air and seek medical attention if ill feelings persist. In case of eye and skin contact, imme- diately flush with plenty of water for 15 minutes and

seek medical attention if irritation persists. KEEP OUT OR REACH OF CHILDREN.

All primers, cleaners, and cements must meet all local codes and applicable standards of the American Society For Testing Materials Standards.

Before using primers, cleaners, and cements, stir or shake, mak- ing sure contents are liquid. Do not use if found to be lumpy or jelly-like.

1.Cut pipe ends squarely removing all burrs and dirt.

2.Dry fit pipe and fittings to be connected for proper fit.

3.Clean pipe and fitting with a primer/cleaner.

4.Apply a thin coat of cement to fitting, avoiding puddling inside.

5.Apply a liberal coat of cement to pipe leaving no voids.

6.QUICKLY assemble parts while cement is flui!! If you wait too long, re-coat pipes.

7.Push pipe completely into socket of fitting, turning as it goes until it bottoms.

8.Hold pipe and fitting together for 30 seconds. Then carefully clean off"excess with a cloth. Allow connections a sufficient

time to cure before disturbing.

9.Remember that vent pipes must be adequately and securely supported.

*NOTE: Two 45 o elbows are equivalent to one 90 o elbow. One 90 ° elbow equals 5 feet of equivalent vent length.

2O

Page 20
Image 20
Kenmore 153.33298, 153.33296, 153.332870HA Installation Instructions contd, Venting contd, I I Groundorsnow, inside bldg