Installation Instructions (cont'd)
2.The convertible dement is located behind the lower access
panel of the water heater. Remove the two screws securing the access panel, and remove panel.
5.Lower Element: LiE out the tab as shown to undip the ter- minal cover from the thermostat. The terminal cover can now be removed from the thermostat.
L_ oul _b Io uncl¥
tlrmlr_l covlr fro_
)ACKET
TERMINAL | COYER | PLASTIC | TABS ON | |
CLIPPED | TO TILER- | |||
|
| |||
Hos'rAT | AT THIS | TERMINAL | COVER | |
POINT |
| |||
| HOLD IT | IN | ||
|
| |||
|
| PLACE, |
|
3.Remove the adjustment dial from the thermostat by gently pulling it directly away from the thermostat.
4.Open the flap of insulation to expose the opening.
;!i
m
!LOWER THERMOSTAT
6.Remove the screws from terminal 2 of the element, and move the looped end of the wire aside.
7.The buss bar is labeled 5500 W. Place the buss bar over terminals 2 and 3 with the 5500 W visible. Install the extra screw provided into terminal 3.
5500W
8.The wire removed from terminal 2 has a looped end. It must remain looped and now be placed (as shown) on top of the buss bar, over the opening of terminal 2, and secured using the remaining screw.
11