Kenmore 153.327466 40 GAL IJnstallation Instructions, contd, Temperature=Pressure, Relief Valve

Models: 153327465 40 GAL 153.327865 327266_J 40 GAI SHORT 153 327566 50 GAE 153327265 40 GA! SHORT 153.327366 153.327565 50 GAL 153.327866 80 GAL 153.327666 153O327165_' 30 GAT 153.327466 40 GAL SHORT 153.327365 153327166 30 GAI SHORT 153.327665

1 32
Download 32 pages 23.87 Kb
Page 9
Image 9
IJnstallation Instructions

IJnstallation Instructions

Temperature=Pressure

Relief Valve

_k WARNIfNG

At the time of manufacture this water heater was provided with a combination temperature-pressures relief valve cer- tified by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equip-

ment or materials, as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Not Water

Supply Systems, and the current edition of ANSI Z21,22 and the code requirements of ASHE+ If replaced, the valve must meet the requirements of local codes, but not less than a combination temperature and pressure relief valve certified as meeting the requirements for Relief Valves and Automatic Gas Shutoff Devices for Hot Water Supply Systems, ANSI Z21.22 by a nationally recognized testing laboratory that maintains periodic inspection of production of listed equipment or materials.

The valve must be marked with a maximum set pressure not to exceed the marked hydrostatic working pressure of the water heater (150 Ibs. p.sJ.) and a discharge capacity not less than the water heater input rate as shown on the model rating plate. (Electric heaters - watts divided by 1000 x 3412 equal BTU/Hro rate.)

Your local jurisdictional authority, while mandating the use

of a temperature-pressure relief valve complying with ANSI Z21.22 and ASME, may require a valve model differ- ent from the one furnished with the water heater.

Compliance with such local requirements must be satisfied by the installer or end user of the water heater with a

locally prescribed temperature-pressure relief valve installed in the designated opening in the water heater in place of the factory furnished valve.

For safe operation of the water heater, the relief valve must not be removed from it's designated opening or

plugged.

The temperature-pressure relief valve must be installed directly into the fitting of the water heater designated for the relief valve. Position the valve downward and provide tubing so that any discharge will exit only within 6 inches above, or at any distance below the structural floor. Be cer- ta!nth_t .nocontact ismade with any th,e e!ectrical p_rt+

The dischargeopening must not be blocked or reduced in

sizeunder any circumstances.Excessive length,over 30 feet, or use of more than four elbows can cause restriction

and reduce the discharge capacity of the valve°

No valve or other obstruction is to be placed between the relief valve and the tank. D,o not connect tubing directly to discharge drain unless a 6 air gap is provided. To prevent bodily injury, hazard to life, or property damage, the relief valve must be allowed to discharge water in quantities should circumstances demand. If the discharge pipe is not connected to a drain or other suitable means, the water flow may cause property damage.

The Discharge Pipe:

,Must not be smaller in size than the outlet pipe size of the valve, or have any reducing couplings or other restriction+

Must not be plugged or blocked+

Must be of material listed for hot water distribution.

Must be installed so as to allow complete drainage of both the temperature-pressure relief valve, and the dis. charge pipe.

Must terminate at an adequate drain.

Must not have any valve between the relief valve and tank,

(cont'd)

_k WARNING

The temperature-pressure relief valve must be manually operated at least once a year. Caution should be taken to ensure that (I) no one is in front of or around the outlet

of the temperature-pressure relief valve discharge line, and (2) the water manually discharged wilt not cause any bodily injury or property damage because the water may be extremely ho_

If after manually operating the valve, it fails to completely reset and continues to release water, immediately, close the cold water inlet to the water heater, follow the drain-

ing instructions, and replace the temperature-pressure relief valve with a new one.

HOT

COLD

HOT

PRESSURE

RELIEF VALVE

(Do not cap or plug)

T&P REUEF

 

VALVE FROEE

'TEMPERATURE.

 

PRESSURE

 

REUEF VALVE

Page 9
Image 9