Note: The generator set will not start and circuit board damage may occur if the battery is connected in reverse.
Figure 1-22 shows the location of the engine starting battery. Standard battery cables provide easy connection to the battery. Use the following procedure to install and connect the battery.
1 |
1. Engine starting battery location |
Figure 1-22 Battery Location, Air Intake End
Battery Installation Procedure
1.Ensure that the starting battery is fully charged before placing the battery in service.
2.Clean the battery posts and/or adapters if necessary.
3.Install the battery post adapters, if needed.
4.Place the battery in the housing.
5.Verify that the controller master switch is in the OFF position.
6.Connect the positive (+) lead to the engine starting battery.
7.Connect the negative (--) lead to the engine starting battery.
Refer to the generator set Operation Manual and the battery manufacturer’s instructions for battery maintenance instructions.
Section 1 Installation 25 |