TP-6516 4/0918 Section1 Installation

1.4.1 Exhaust Requirements

Carbon monoxide.
Can cause severe nausea,
fainting, or death.
The exhaust system must be
leakproof and routinely inspected.
WARNING
Generator set operation. Carbon monoxide can cause
severe nausea, fainting, or death. Carbon monoxide is an
odorless,colorless, tasteless, nonirritating gas that can cause
deathif inhaled for even a short time. Avoidbreathing exhaust
fumes when working on or near the generator set. Never
operatethe generator set inside a building. Never operate the
generator set where exhaust gas could seep inside or be
drawninto a potentially occupied building through windows,air
intake vents, or other openings.
The exhaust system is complete for generator sets
installed outdoors. Do not install this generator set
indoors.
Figure 1-6 gives the exhaust flow and temperature at
rated load. The engine exhaust mixes with the
generator set cooling air at the exhaust end of the
enclosure. Mount the generator set so that the hot
exhaust does not blow on plants or other combustible
materials. Maintain the clearances shown inFigure 1-5.
Exhaust System 60 Hz
Exhaust flow at rated kW,
m3/min. (cfm)
12 kW 3.8(135)
17/18 kW 5.3 (187)
Exhaust gas temperature exiting
the enclosure at rated kW, _C(_F) 216 (420)
Figure 1-6 Exhaust Flow and Temperature

1.4.2 Air Requirements

The generator set requires correct air flow for cooling
and combustion. The inlet and outlet openings in the
sound enclosure provide the cooling and combustion
air. Figure 1-7 shows the locations of the cooling air
intakeand exhaust vents. Inspect the air inlet and outlet
openings inside and outside the housing to ensure that
the air flow is not blocked.
GM51561
2
1. Exhaust outlet
2. Alternator air intake (both sides)
3. Engine air intake
3
1
3
Figure 1-7 Cooling Air Intake and Exhaust
Model
Air Requirements, m3/min. (cfm)
Hz
Cooling
Air
Combustion
Air
Tota l Inlet
Air
12 kW 60 26.9 (950) 1.1 (39.2) 28.0 (990)
50 22.4(790) 0.9 (32.6) 23.4(826)
17/18
kW
60 28.0(989) 1.62 (57.3) 29.6 (1045)
50 22.6(798) 1.42 (50.1) 24.0 (848)
Figure 1-8 Air Requirements
1.5 Power Supply
Power must be supplied from a source that is GFCI
protected to the generator set location for the battery
charger and the optional carburetor heater. See
Section 1.8. Connect power from a circuit on the
essential loads panel to the 120-VAC receptacles.
Figure 1-9 lists the power requirements for the battery
charger and accessories.
Equipment
Power Requirement, Max.
Watts Amps Volts
Battery charger 192 1.6
120
Carburetor heater:
12 kW 38 0.32
17/18 kW 40 0.34
Battery heater 110 0.92
Figure 1-9 Power Requirements