1.4.1Exhaust Requirements

WARNING

Carbon monoxide.

Can cause severe nausea, fainting, or death.

The exhaust system must be leakproof and routinely inspected.

1

2

1.Exhaust outlet

2.Alternator air intake (both sides)

3.Engine air intake

3

3

GM51561

Generator set operation. Carbon monoxide can cause severe nausea, fainting, or death. Carbon monoxide is an odorless, colorless, tasteless, nonirritating gas that can cause death if inhaled for even a short time. Avoid breathing exhaust fumes when working on or near the generator set. Never operate the generator set inside a building. Never operate the generator set where exhaust gas could seep inside or be drawn into a potentially occupied building through windows, air intake vents, or other openings.

The exhaust system is complete for generator sets installed outdoors. Do not install this generator set indoors.

Figure 1-6 gives the exhaust flow and temperature at rated load. The engine exhaust mixes with the generator set cooling air at the exhaust end of the enclosure. Mount the generator set so that the hot exhaust does not blow on plants or other combustible materials. Maintain the clearances shown in Figure 1-5.

Exhaust System

60 Hz

 

 

Exhaust flow at rated kW,

 

m3/min. (cfm)

 

12 kW

3.8 (135)

17/18 kW

5.3 (187)

 

 

Exhaust gas temperature exiting

 

the enclosure at rated kW, _C (_F)

216 (420)

 

 

Figure 1-6 Exhaust Flow and Temperature

1.4.2Air Requirements

The generator set requires correct air flow for cooling and combustion. The inlet and outlet openings in the sound enclosure provide the cooling and combustion air. Figure 1-7 shows the locations of the cooling air intake and exhaust vents. Inspect the air inlet and outlet openings inside and outside the housing to ensure that the air flow is not blocked.

Figure 1-7 Cooling Air Intake and Exhaust

 

 

Air Requirements, m3/min. (cfm)

 

 

Cooling

Combustion

Total Inlet

Model

Hz

Air

Air

Air

12 kW

60

26.9 (950)

1.1 (39.2)

28.0 (990)

 

 

 

 

50

22.4 (790)

0.9 (32.6)

23.4 (826)

 

 

 

 

 

 

17/18

60

28.0 (989)

1.62 (57.3)

29.6 (1045)

 

 

 

 

kW

50

22.6 (798)

1.42 (50.1)

24.0 (848)

 

 

 

 

 

 

Figure 1-8 Air Requirements

1.5 Power Supply

Power must be supplied from a source that is GFCI protected to the generator set location for the battery charger and the optional carburetor heater. See Section 1.8. Connect power from a circuit on the essential loads panel to the 120-VAC receptacles. Figure 1-9 lists the power requirements for the battery charger and accessories.

 

Power Requirement, Max.

 

 

 

 

Equipment

Watts

Amps

Volts

Battery charger

192

1.6

 

 

 

 

 

Carburetor heater:

 

 

 

12 kW

38

0.32

120

17/18 kW

40

0.34

 

 

 

 

 

Battery heater

110

0.92

 

 

 

 

 

Figure 1-9 Power Requirements

18 Section 1 Installation

TP-6516 4/09

Page 18
Image 18
Kohler 12RESM1 manual Power Supply, Exhaust Requirements, Air Requirements