Step 4. Field Wiring
CAUTION
Label all wires prior to discon- nection when servicing controls. Wiring errors can cause improper and dangerous appliance opera- tion.
CAUTION
Ensure that wires are positioned away from hot surfaces and sharp edges.
CAUTION
Do not connect the optional wall switch for burner operation to a 120 Volt AC power supply.
Refer to Section A for millivolt appliances and Section B for electronic appliances. The gas valve is set in place and
A. SIT and Honeywell Millivolt Wiring
(See Figure 45)
1. Select any of the following optional controls:
2. If
3. Wire the control within the millivolt control circuit using the 15 feet of 2 conductor wire supplied with the unit . Caution: do not connect the optional wall switch to a 120V power supply.
4.Alternatively, the appliance may be operated without the use of the controls indicated in step 1, solely by manipulating the gas valve control knob. In order to use this method, twist the free ends of the two conductor wire (which would otherwise go to the standard ON/OFF switch or Optional Switch) together as shown in Figure 45. Note: Wire is located inside the control compartment
Note: The supplied 15 feet of 2 conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose inside the control compartment.
B. Electronic Wiring (See Figure 47) –
Note: The electronic appliance must be con- nected to the main power supply.
The junction box is located on the right side of the appliance. It contains a factory installed and wired outlet box (duplex receptacle). Also, an optional
1.
2.If the
3. Connect the power supply wires (including the ground supply wire) as shown in Figure
47.(If the
4. Locate and install a low voltage (24V) wall- mounted switch or thermostat (both field- provided)in the desired location.
5.Connect the low voltage wire, located inside
Note: The supplied 15 feet of 2 conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose inside the control compartment.
6.Insert the control circuit plug into the un- switched receptacle of the outlet box.
7.After wiring is complete, mount the outlet box to the
Note: The gas
Step 5. Wiring - Optional Forced Air Blower Kit
FBK-100, FBK-200 and FBK250 Kits
(See Figure 47) -
An electrical outlet box (receptacle) is factory
TP
*
*Twist wires together to operate unit solely by manipulating the gas valve control knob; or connect wires to optional control switch (wall switch, remote control or wall thermostat to
operate unit.
| TP | TH TP |
Thermopile |
| TH |
|
| |
* Optional | Schematic | |
Control Switch | Representation | |
|
Only
See Figure 14 on Page 9 for Optional Electrical Inlet Knockout Location
| |
| Junction Box |
| and Duplex |
*Narrow (2 1/8" Wide) | Receptacle |
| |
|
Optional
Box (Left Side Shown)
Figure 46
• If any of the original wire as supplied must be replaced, it must be replaced with Type AWM 105 C - 18 gage wire.
*Optional Kits Installed - ON/OFF wall switch, unit mounted burner ON/OFF switch, wall thermostat or remote control.receiver.
Figure 45 - Millivolt Wiring Diagram
NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.
23