Lennox Hearth LMDV-35 Series, LMDV-4035-CPM Field Wiring, Wiring - Optional Forced Air Blower Kit

Models: LMDV-3530-CNM LMDV-35 Series LMDVR-3328-CNE LMDV-4035-CNE LMDV-4035-CPM LMDVT-3328-CNM LMDV-40 Series LMDV-33 Series LMDV-4035-CNM LMDVR-3328-CPM LMDVR-3328-CNM LMDVT-3328-CNE LMDV-3530-CNE LMDV-3530-CPM LMDVT-3328-CPM

1 36
Download 36 pages 28.89 Kb
Page 23
Image 23
Step 4. Field Wiring
Field Wired
Factory
Wired

Step 4. Field Wiring

A. SIT and Honeywell Millivolt WiringCAUTION

Label all wires prior to discon- nection when servicing controls. Wiring errors can cause improper and dangerous appliance opera- tion.

B. Electronic Wiring (See Figure 47) – CAUTION

Ensure that wires are positioned away from hot surfaces and sharp edges.

Step 5. Wiring - Optional Forced Air Blower KitCAUTION

Do not connect the optional wall switch for burner operation to a 120 Volt AC power supply.

Refer to Section A for millivolt appliances and Section B for electronic appliances. The gas valve is set in place and pre-wired at the factory on both models.

A. SIT and Honeywell Millivolt Wiring

(See Figure 45)

1. Select any of the following optional controls: appliance-mounted (rocker switch) or wall- mounted switch, thermostat, or one of the optional remote control kits. If appliance- mounted ON/OFF control is selected mount it in the gas valve mounting bracket.

2. If wall-mounted ON/OFF control or ther- mostat is selected mount it in a convenient location on a wall near the fireplace.

3. Wire the control within the millivolt control circuit using the 15 feet of 2 conductor wire supplied with the unit . Caution: do not connect the optional wall switch to a 120V power supply.

4.Alternatively, the appliance may be operated without the use of the controls indicated in step 1, solely by manipulating the gas valve control knob. In order to use this method, twist the free ends of the two conductor wire (which would otherwise go to the standard ON/OFF switch or Optional Switch) together as shown in Figure 45. Note: Wire is located inside the control compartment

Note: The supplied 15 feet of 2 conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose inside the control compartment.

B. Electronic Wiring (See Figure 47)

Note: The electronic appliance must be con- nected to the main power supply.

The junction box is located on the right side of the appliance. It contains a factory installed and wired outlet box (duplex receptacle). Also, an optional field-provided junction box with recep- tacle may be installed at the front of the control compartment on either side of the cabinet. See Figure 46. It will be held in place by a conduit fitting and locknut (field-provided).

1. Routea3-wire120Vac60Hz1phpowersupply to the appliance junction box.

2.If the factory-provided outlet/junction box at the right rear of the fireplace is being used, remove the outlet box from the junction box by removing two screws.

3. Connect the power supply wires (including the ground supply wire) as shown in Figure

47.(If the field-provided J-box/outlet box is being used, all of the outlet box wiring must be field-provided).

4. Locate and install a low voltage (24V) wall- mounted switch or thermostat (both field- provided)in the desired location.

5.Connect the low voltage wire, located inside thecontrolcompartment,tothewall-mounted switch or thermostat.

Note: The supplied 15 feet of 2 conductor wire has one end of each conductor connected to the gas valve circuit and the other end of each conductor placed loose inside the control compartment.

6.Insert the control circuit plug into the un- switched receptacle of the outlet box.

7.After wiring is complete, mount the outlet box to the J-Box.

Note: The gas valve-mounted ON/OFF switch is shown in Figure 47. It is integral with the gas valve and should be set to the ON position.

Step 5. Wiring - Optional Forced Air Blower Kit

FBK-100, FBK-200 and FBK250 Kits

(See Figure 47) -

An electrical outlet box (receptacle) is factory -provided for the installation of the FBK-100, FBK-200 and FBK-250forced air blower kits. (An optional field-provided outletbox/J-Box may also be used. Electrical power must be connected to either of these receptacles in order to operate these blowers. Install the blower kits according to the installation instructions provided with the kits.

TP

*

*Twist wires together to operate unit solely by manipulating the gas valve control knob; or connect wires to optional control switch (wall switch, remote control or wall thermostat to

operate unit.

 

TP

TH TP

Thermopile

 

TH

 

 

* Optional

Schematic

Control Switch

Representation

 

Only

See Figure 14 on Page 9 for Optional Electrical Inlet Knockout Location

 

*Field-Provided

 

Junction Box

 

and Duplex

*Narrow (2 1/8" Wide)

Receptacle

 

J-Box Required

 

Optional J-Box/Outlet

Box (Left Side Shown)

Figure 46

• If any of the original wire as supplied must be replaced, it must be replaced with Type AWM 105 C - 18 gage wire.

*Optional Kits Installed - ON/OFF wall switch, unit mounted burner ON/OFF switch, wall thermostat or remote control.receiver.

Figure 45 - Millivolt Wiring Diagram

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

23

Page 23
Image 23
Lennox Hearth LMDV-35 Series Field Wiring, Wiring - Optional Forced Air Blower Kit, Millivolt Wiring Diagram