| Combustible | Non | Finished Wall |
| |
| Mantel and Trim | Combustible | Header |
|
|
| (See Note) | Material |
| Sheet Metal | |
|
|
| |||
|
|
| Spacer |
| |
|
| 12" |
| 5" | Top Of Fireplace |
|
| Max. |
| ||
18 5/8" |
|
|
|
| |
|
|
|
|
| |
| Min. |
|
|
|
|
| 18" |
| 3 Sheet Metal Screws | ||
|
|
| |||
|
|
| #10 x 3/4" Max. Flat Head | ||
| 12" |
|
|
|
|
| Min. | 10" |
|
|
|
|
| Min. | Fireplace Opening | ||
|
|
|
Note: Mantel At Minimum Height Should Be Affixed to Framing Hinge Posts At Right And Left Of The Fireplace. Do Not Use Molly Bolts In Front Of The Fireplace.
Typical Installation
Figure 23
INSTALLATION ACCESSORIES
The following accessory items are available for use in the installation of this appliance.
| 12" Length | 10KL1 |
| 24" Length | 10KL2 |
| 36" Length | 10KL3 |
Security 10" | Adjustable Length | 10KAL |
|
|
|
Elbow | 10" X 45 Degree | 10KE45 |
FINISHING REQUIREMENTS
Wall Details and Combustible Mantels
Complete finished interior wall. To install the appliance facing flush with the finished wall, position framework to accommodate the thick- ness of the finished wall (Figure 23 ). Both Figures 23 and 24 show a combustible mantel shelf projecting a maximum of 12" (305 mm) from the wall, and which must be installed a minimum distance of 12" (305mm) from the top of the firebox opening. No other mantel length/height combinations are allowable for this fireplace.
A hearth extension is not required with this appliance. Any hearth extension used is for appearance only and does not have to conform to standard hearth extension installation re- quirements.
Note: Combustible wall finish materials and/or surround materials must not be allowed to encroach the area defined by the appliance front face (black sheet metal). Never allow combustible materials to be positioned in front of or overlapping the appliance front face.
0" Clearance to Combustible Side Wall
Max. Projection 12" (305 mm)
Combustible | 60" |
Mantel | |
| (1524 mm) |
| Min. to |
| Ceiling |
| 12" Min. |
| (305 mm) |
Figure 24
COLD CLIMATE INSULATION
If you live in a cold climate, seal all cracks around your appliance with noncombustible material and wherever cold air could enter the room. It is especially important to insulate outside chase cavity between studs and under floor on which appliance rests, if floor is above ground level.
Brace Support | BV 10" | 10KBS |
|
|
|
Firestop | BV 10" | 10KBF |
12
NOTE: DIAGRAMS & ILLUSTRATIONS NOT TO SCALE.