TROUBLESHOOTING
NOTE: When troubleshooting the gas control system, be sure the external gas shut off valve, located at the gas supply inlet is in the “ON” position.
IMPORTANT: Call your gas supplier or plumber for additional help with any gas control problem. Valve system troubleshooting should only be accomplished by a qualified service technician.
SYMPTOM | PROBABLE CAUSE | CORRECTIVE ACTION |
Thin black coating | Improper log or ember | See Log Set and Ember Installation. |
(soot) forms on the | placement. |
|
viewing glass, logs, or |
| Check for obstructions in vent pipe, check for proper restrictor setting. See Flue Restric- |
firebox. | Blocked flue. | |
|
| tors. |
| Improper air shutter | See Air Shutter Adjustment. |
| setting. |
|
Humming or whistling | Normal operating noise. | See Quiet Operation. The noise may be reduced by slightly turning the flame down. Turning |
coming from fireplace. |
| the flame down will reduce the heat output of the fireplace. |
| Dirt in burner orifice. | Clean orifice. |
|
|
|
A change in flame | A change in gas pres- | Have your gas supplier check for correct gas pressure (7” W.C. natural gas; 11” W.C. LP |
appearance or burner | sure. | gas). |
operation. |
| See Log Set and Ember Installation. |
| Improper ember or log | |
|
| |
| placement. |
|
|
|
|
Pilot will not light. | No gas supplied to unit. | Turn on gas. |
| Air in line. | To purge, hold in control knob in pilot position for |
| Defective igniter (no | Check for spark at electrode and pilot, if no spark and electrode wire is properly connected, |
| spark at electrode). | replace igniter. |
| The valve control knob | See Lighting Instructions. |
| is not turned to “pilot” |
|
| and pushed in. |
|
|
|
|
Pilot will not stay lit | Pilot flame is not sur- | Check pilot flame adjustment (see Maintenance and Servicing section). |
after carefully following | rounding thermocouple. |
|
lighting instructions. | Thermocouple not | Check the connection between the thermocouple lead and the valve. Turn control knob to |
| ||
| generating sufficient | “pilot” and push in and light pilot. While lit, take millivolt reading at lead going into valve’s |
| voltage. | CPU. Minimum reading should be 17 millivolts. If less, replace thermocouple. |
| Air in gas supply line. | Purge air in pilot gas line by holding in control knob at “pilot” and sparking igniter. The air |
|
| in the line may take up to several minutes to purge. |
Main burner will not | Pilot has gone out. | See Lighting Instructions. |
burn. | Rocker switch or | Disconnect rocker switch and thermostat wires at terminals 1 and 3 on valve. Jumper |
| ||
| thermostat wires are | across from 1 to 3 with pilot lit. If burner comes on either rocker switch or thermostat wir- |
| defective. | ing is not functioning. |
| Thermopile may not be | Make sure thermopile is fully engulfed by the pilot flame. Check thermopile with millivolt |
| meter. With pilot lit and the rocker switch and thermostat off, the millivolt reading with the | |
| generating sufficient | meter connected to valve terminals 1 and 2 should be after 2 minutes at least 325. If the |
| millivolts. | thermopile lead connections are good at terminals 1 and 2 and readings are less than 325, |
|
| replace faulty thermopile. |
23