Approach Values for TXV Systems

° Liquid Line Temperature °F

_

° Outdoor Ambient Temperature °F

=° Approach Temperature °F

6.Compare the approach value with those shown in Table

9.If the values do not agree with those provided in Table 8, add refrigerant to lower the approach temperature or recover refrigerant from the system to increase the approach temperature.

Check Charge Using Normal Operating Pressures Use Table 7 to perform maintenance checks. Table 7 is not a procedure for charging the system. Minor variations in these pressures may be due to differences in installations. Significant deviations could mean that the system is not properly charged or that a problem exists with some component in the system.

Approach Values for TXV Systems

Table 7

506470-01

Issue 1007

Page 16

Page 16
Image 16