Lennox International Inc 4HP18LT manual Flash Codes cont, 24VAC Power Wiring

Models: 4HP18LT

1 28
Download 28 pages 8.37 Kb
Page 21
Image 21
24VAC Power Wiring

Every time the module powers up, the last ALERT LED flash code that occurred prior to shutdown is displayed for

60 seconds. The module will continue to display the previous flash code until the condition returns to normal or 21VAC is removed from the module. TRIP and ALERT LEDs flashing at the same time means control circuit voltage is too low for operation.

24VAC Power Wiring

The diagnostic module requires a constant nominal 24VAC power supply. The wiring to the module’s R and C terminals must be directly from the indoor unit or thermostat. The module cannot be powered by R and C terminals on the defrost board without experiencing nuisance alerts.

Flash Codes (cont.)

Table 11

506470-01

Issue 1007

Page 21

Page 21
Image 21
Lennox International Inc 4HP18LT manual Flash Codes cont, 24VAC Power Wiring