Beforestartingunit,makesuretheoiltankisadequately filledwithcleanNo,1orNo,2furnaceoil,
NOTE - Water, rust or other contaminants in oil supply sys- tem will cause malfunction and failure of the internal parts of the fuel pump.
CAUTION
Table 7
| Nozzle Size, |
| Input | Output |
| Temp | |
O23V | Spray Angle, | Pump | Rating | Rating |
| Rise | |
Unit | & Pattern |
| PSIG | BTU/Hr | BTU/Hr | Head | F° |
° A | 100 | 70,000 | 57,000 | FB0 | |||
° B | 100 | 90,000 | 72,000 | FB0 | |||
° B | 140 | 105,000 | 84,000 | FB3 | |||
° B | 140 | 119,000 | 105,000 | FB3 | |||
° B | 140 | 140,000 | 112,000 | FB6 | |||
° B | 140 | 154,000 | 125,000 | FB6 |
1, Set thermostat for heating demand and turn on electri- cal supply to unit,
2, Check initial air adjustment, All units are equipped with an air adjustment dial on the right side of the burner, See burner parts arrangement illustration.
3, Turn unit on. Place a can or container under the bleed port located on the fuel pump. Loosen nut on bleed port to release air and oil mixture from fuel line. Allow mixture to escape until a steady stream of oil is emitted from the port. Drain at least 1/2 pint of oil from the pump, Retighten the nut on bleed port. If lockout oc-
curs, press reset button and continue with bleed pro- cedure,
NOTE - A
4, If burner fails to start, push reset button on primary safety control and the burner motor reset button. See part arrangement illustration,
CAUTION
5, If the burner fails to light again, refer to the trouble- shooting section in this manual,
Measuring Fuel Pump Pressure
Measure fuel pump pressure with unit off. Attach pressure gauge to pump outlet, Turn unit on and check pressure and compare to table 7. Adjust if necessary,
Measuring Temperature Rise
To measure temperature rise, place plenum thermometers in warm air and return air plenums, Locate thermometer in warm air plenum where thermometer will not "see" the heat exchanger to prevent it from picking up radiant heat. Set thermostat to its highest setting to start unit, After plenum thermometers have reached their highest and steadiest readings, subtract the readings, The difference in temper- atures in the supply and return air plenums should approxi- mate the temperature rise range listed in table 7 and the appliance rating plate, If the rise is above the range shown in the table, check for high static pressure.
Adjusting Limit Control
DO NOT adjust limit control - it is preset at the factory,
Adjusting and Testing Burner
The following instructions are essential to the proper op- eration of O23V series oil furnaces, To prevent sooting, these instructions must be followed in sequence:
1,
A minimum of 0,03 draft must be established without
the burner in operation. With the burner in operation, the draft should be 0,04 to 0.05. This is VERY critical to the flame retention head burners.
Oil furnace installations also require careful inspection to make sure the chimney is in good shape and can ac- commodate the products of combustion, The temper- ature in the unconditioned space will also affect the draft if long vent connectors are allowed to get too cold,
2.Overfire
A reading of the overfire draft should be 0.02 less than the reading found in the vent connector. If a positive reading is seen at this point, the combustion fan is
pumping too much air into the heat exchanger. Make the necessary adjustments at the air adjustment dial.
3, Smoke
Using a smoke test gun adjust the air inlet shutter so that you will have just a trace of smoke, Somewhere between a 0 and #1 smoke, This is the starting point, Do not stop here.
4, CO2
eration" will be determined. This window of operation establishes some tolerance, The tolerance the install-
er builds in provides room within the