Burner Motor Motor does not come up to speed and trips out on overload. Turn off power and rotate blower wheel by hand to check for binding or excessive drag.

Causes

Correction

 

Low line voltage

Check voltage

at power source.

 

Correct cause of voltage drop or the

 

call power company.

Pump or blower overloading motor

Correct

cause

of overloading.

Faulty motor

Replace

motor.

 

Source

Poor Fire

Flame Detector

Procedure

After burner fires,

immediately jumper across flame detector terminals at

the primary control.

If burner continues to run, this may be due to poor fire. Inspect fire.

If fire is good, fault is in the flame detector.

Check detector circuit.

Causes

Unbalanced fire

Too much air - -lean short fire

Too little air - - long dirty fire

Excessive draft

Too little draft or restriction

Dirty cad cell face

Faulty cad cell - exceeds 15000 hms Loose or defective cad cell wires

Correction

Replace nozzle

Reduce combustion air - check combustion.

Increase combustion air - check combustion.

Adjust barometric damper for correct draft.

Correct draft or remove restriction.

Clean cad cell face.

Replace cad cell.

Secure connections or replace cad cell holder and wire leads.

Primary Control olf burner locks out on

safety, fault is in the pri- mary control.

SourceProcedure

Thermostat Check thermostat.

Limit Control Connect voltmeter between line voltage connections to primary control (black & white leads). If burner cycles due to power interruption, it is cycling on limit.

Primary control circuit defective

Causes

Heat anticipator set too low

Vibration at thermostat

Thermostat in the path of a warm air draft

Dirty furnace air filters

Blower running too slow

Blower motor seized or burned out

Blower bearings seized

Blower wheel dirty

Blower wheel in backward

Wrong motor rotation

Restrictions in return or supply air system

Adjustable limit control set too low

Replace primary control.

Correction

Correct heat anticipator setting.

Correct source of vibration.

Shield thermostat from draft or relocate.

Clean or replace filter.

Increase blower speed to maintain proper temp. rise.

Check for high static pressure.

Check HEAT selector pin per wiring diagram (figure 18, page 16).

Replace motor.

Replace bearings and shaft.

Clean blower wheel.

Reverse blower wheel.

Replace with properly rotating wheel.

Correct cause of restriction.

Reset limit to maximum stop setting.

table continued on next page