Lennox International Inc O23V-140 One-PipeSystems, Installation, Clearances, inches mm, Cat. No

Models: O23V2-90 O23V-90 O23V4-105 O23V5-154 O23V3-70 O23V-154 O23V5-140 O23V2-70 O23V-70 O23V-140 O23V-120 O23V-105 O23V3-105 O23V3-90 O23V4-120 O23V3-120

1 24
Download 24 pages 55.93 Kb
Page 12
Image 12
One-Pipe Systems

One-Pipe Systems

CAUTION

The burner is shipped with fuel pump set for one-pipe op- eration. For one-pipe systems, the oil supply pipe is con- nected to the inlet tap on the pump. A one-pipe system should only be used where there is gravity oil flow to the

pump and the pipe is not run at any point above the oil level in the tank.

1. Connect the inlet pipe to the pump inlet. Start the bum-

er,

2.Arrange the primary burner control for continuous op- eration during purging (see figure 15).

3.Turn the bleed valve one turn counterclockwise to open.

4.Bleed the unit until all air bubbles disappear.

NOTE - Hurried bleeding will prevent the unit from op- erating properly.

5.Tighten the bleed valve securely.

Two-Pipe Systems

If the installation requires a two-pipe operation, install the bypass plug included in the bag which is attached to the pump. To convert the pump, install the bypass plug accord- ing to the provided pump instructions. Notice in the two- pipe system the return pipe must terminate in the tank 3" (76 mm) to 4" (102 mm) above the supply inlet. Ensure the return pipe terminates at the correct measurement or air may escape into the system. This could result in loss of prime.

NOTE- If using an outside tank in cold climates a number one fuel or an oil treatment is strongly recommended.

1.Remove 1/4" plug from return port.

2.Insert bypass plug and tighten it (see figure 16).

3.Attach the return and inlet pipes. Start the burner. Air bleeding is automatic.

NOTE - If a faster bleed is necessary, open the bleed valve.

4.The return pipe must terminate 3" to 4" above the sup- ply pipe inlet (see figure 16).

NOTE - If the return pipe does not terminate where it should, air may enter the system, and prime may be lost.

An oil filter is required for all models. Install filter inside the building between the tank shut-off valve and the burn-

er. Locate filter close to burner for easy maintenance. Table 5 lists the filters for the O23V furnace.

 

Table 5

 

Installation

Clearances

inches (mm)

Oil Filters

 

Cat. No.

10 micronfilter (no

mounting bracket)

81 P89

10 micron replacement cartridge for filter, 45 gph

53P93

Filter restriction indicator gauge

53P90

Consult burner manufacturer's instructions packaged with unit for further details concerning oil supply pipe connec- tions.

After oil piping is completed, carefully check all piping con- nections (factory and field) for oil leaks,

Oil Pipe Heater (Optional)

A heater for the oil pipe is available for applications that are located in cold climates. The heater warms the oil pipe to assist the initial start-up.

Wiring must conform to current National Electric Code ANSI/NFPA No, 70, or Canadian Electric Code Part I, CSA

Standard C22.1, and local building codes. Refer to figure 18 for wiring diagram and to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size, Select the proper supply circuit conductors in accor- dance with tables 310-16 and 310-17 in the National Electric Code, ANSI/NFPA No, 70 or tables 1 through 4 in the Canadian Electric Code, Part I, CSA Standard C22.1.

This unit is provided with holes for conduit, Reducer washers are provided for sizing the hole to allow for smaller conduit. Use provided caps to seal holes not used. Refer to figure 17 for the terminal designations on the A54 blower control board, Refer to figure 18 for unit schematic wiring diagram with typical field wiring.

Separate openings are provided for 24V low voltage and for line voltage. Refer to figure 1 for specific location.

WARNING

1. Refer to the appliance rating plate for proper fuse size.

Page 12

505082M 10_5

Page 12
Image 12
Lennox International Inc O23V-140 One-PipeSystems, Installation, Clearances, inches mm, Oil Filters, Cat. No, 81 P89