One-Pipe Systems
CAUTION
The burner is shipped with fuel pump set for
pump and the pipe is not run at any point above the oil level in the tank.
1. Connect the inlet pipe to the pump inlet. Start the bum-
er,
2.Arrange the primary burner control for continuous op- eration during purging (see figure 15).
3.Turn the bleed valve one turn counterclockwise to open.
4.Bleed the unit until all air bubbles disappear.
NOTE - Hurried bleeding will prevent the unit from op- erating properly.
5.Tighten the bleed valve securely.
If the installation requires a
NOTE- If using an outside tank in cold climates a number one fuel or an oil treatment is strongly recommended.
1.Remove 1/4" plug from return port.
2.Insert bypass plug and tighten it (see figure 16).
3.Attach the return and inlet pipes. Start the burner. Air bleeding is automatic.
NOTE - If a faster bleed is necessary, open the bleed valve.
4.The return pipe must terminate 3" to 4" above the sup- ply pipe inlet (see figure 16).
NOTE - If the return pipe does not terminate where it should, air may enter the system, and prime may be lost.
An oil filter is required for all models. Install filter inside the building between the tank
er. Locate filter close to burner for easy maintenance. Table 5 lists the filters for the O23V furnace.
| Table 5 |
|
Installation | Clearances | inches (mm) |
Oil Filters |
| Cat. No. |
10 micronfilter (no | mounting bracket) | 81 P89 |
10 micron replacement cartridge for filter, 45 gph | 53P93 |
Filter restriction indicator gauge | 53P90 |
Consult burner manufacturer's instructions packaged with unit for further details concerning oil supply pipe connec- tions.
After oil piping is completed, carefully check all piping con- nections (factory and field) for oil leaks,
Oil Pipe Heater (Optional)
A heater for the oil pipe is available for applications that are located in cold climates. The heater warms the oil pipe to assist the initial
Wiring must conform to current National Electric Code ANSI/NFPA No, 70, or Canadian Electric Code Part I, CSA
Standard C22.1, and local building codes. Refer to figure 18 for wiring diagram and to unit nameplate for minimum circuit ampacity and maximum overcurrent protection size, Select the proper supply circuit conductors in accor- dance with tables
This unit is provided with holes for conduit, Reducer washers are provided for sizing the hole to allow for smaller conduit. Use provided caps to seal holes not used. Refer to figure 17 for the terminal designations on the A54 blower control board, Refer to figure 18 for unit schematic wiring diagram with typical field wiring.
Separate openings are provided for 24V low voltage and for line voltage. Refer to figure 1 for specific location.
WARNING
1. Refer to the appliance rating plate for proper fuse size.
Page 12
505082M 10_5