Communication System

STEP 5 −− ELECTRICAL (Continued) −− Outdoor Control (A175) Jumpers and Terminals

Communication System

The jumper settings and link are default settings and ONLY control system operation if configuration settings in the icomfortt−enabled thermostat are not available.

Non−Communicating System

The unit will operate based on jumper settings and R−TO− DS link on the MAIN CONTROL. All unit setting changes must be done at the MAIN CONTROL. The Lennox ComfortSense® 7000 thermostat may be used, as well as other non−communicating electronic−only thermostats.

The Lennox icomfortt−enabled thermostat must be used in communicating applications.

NOTE Fan cycling routine when activated will cycle the fan ON for five minutes if the outdoor ambient air temperature is between 15ºF and 35ºF and the compressor has been OFF for 25 to 30 minutes. This option is to help reduce the potential for ice build up on the orifice ring during system OFF cycles that are greater than 25 to 30 minutes.

J3 ALL UNITS)

Set up of jumpers on replacement outdoor control.

(HP ONLY) J4

COMPRESSOR SHIFT DELAY

30

SECOND DELAY (DEFAULT)

30

7−SEGMENT

DISPLAY

PUSH

BUTTON

FAN CYCLING

JUMPER ON

FAN ON FOR 5 MINUTES ON

JUMPER OFF

DISABLE (DEFAULT)

OFF

SEE NOTE ABOVE FOR FURTHER DETAILS.

Non−Communicating System J1 (HP ONLY)

DEFROST TERMINATION TEMPERATURE

100

DEGREE

TARGET J3 ALL UNITS)Set up of jumpers on replacement outdoor control.(HP ONLY) J4 J1 (HP ONLY)(TWO−STAGE HEAT PUMP ONLY) J2DS TO R TWO−STAGE UNIT ONLY) 100907050 Manual background

0

SECOND DELAY

0

(TWO−STAGE HEAT PUMP ONLY) J2

SECOND−STAGE LOCK−IN TEMPERATURE

55

DEGREE

TARGET

90 DEGREE TARGET

70 DEGREE TARGET

50 DEGREE TARGET

(DEFAULT)

100 100100 90 9090 70 7070 50 5050

90 1009070 50

(DEFAULT WHEN JUMPER IS REMOVED OR MISSING)

55

 

 

50 45

 

 

40

50

 

 

DEGREE

 

 

TARGET

 

 

55

 

 

50

 

 

45 40

45

 

 

DEGREE

 

 

TARGET

 

 

55

 

 

50 45

 

 

40

40 DEGREE

TARGET (DEFAULT)

55

 

50 45

 

40

DS TO R TWO−STAGE UNIT ONLY)

Cut for Humiditrol® − Enhanced Dehumification Accessory (EDA) applications.

NOTE − LINK NOT APPLICABLE TO ONE−STAGE UNITS. CUTTING LINK WILL HAVE NO AFFECT ON OPERATION OF ONE−STAGE UNITS.