Lennox International Inc Dave Lennox Signature Collection XC21 System Placement

Models: Dave Lennox Signature Collection XC21 System XC21

1 19
Download 19 pages 52.21 Kb
Page 3
Image 3
PLACEMENT

PLACEMENT

STABILIZING UNIT ON UNEVEN SURFACES

INSTALL UNIT AWAY

FROM WINDOWS

TWO 90_ ELBOWS INSTALLED IN LINE SET

#10 X 1/2" LONG SELF−DRILLING SHEET METAL SCREWS

STABILIZING BRACKET (18 GAUGE METAL

WIDTH; HEIGHT AS REQUIRED)

#10 X 1−1/4" LONG HEX HD SCREW AND FLAT WASHER

Concrete slab

plastic anchors (hole drill 1/4")

COIL

BASE PAN

CORNER POST

WILL REDUCE LINE SET VIBRATION

FIGURE 2

SLAB MOUNTING

Install unit level or, if on a slope, maintain slope tolerance of 2 degrees (or 2 inches per 5 feet [50 mm per 1.5 m]) away from building structure.

BUILDING

DISCHARGE AIR

STRUCTURE

 

MOUNTING

SLAB

GROUND LEVEL

FIGURE 3

ELEVATED SLAB MOUNTING USING FEET

EXTENDERS

Use additional 2" SCH 40 male

2" (50.8MM) SCH 40

threaded adapters which can

FEMALE THREADED

be threaded into the female

ADAPTER

threaded

adapters to

make

 

 

additional

adjustments

to the

 

level of the unit.

 

2" (50.8MM)

 

 

 

SCH 40 MALE

 

 

THREADED

 

 

ADAPTER

 

 

 

BASE

LEG DETAIL

FIGURE 4

! IMPORTANT !

Unit Stabilizer Bracket Use

(field−provided):

Always use stabilizers when unit is raised above the factory height.

(Elevated units could become unstable in gusty wind conditions.)

Stabilizers may be used on any unit installed on unstable and uneven surfaces.

FIGURE 5

STEP 2 −− REFRIGERANT PIPING −− Flush- ing Existing Line Set & Indoor Coil

Flush the existing line set per the following instruc- tions. For more information, refer to the Installation and Service Procedures manual available on Dave- Net. CAUTION −DO NOT attempt to flush and re−use ex- isting line sets or indoor coil when the system con- tains contaminants (i.e., compressor burn out).

NOTE − When installing refrigerant lines longer than 50 feet, refer to the Refrigerant Piping Design and Fabrication Guidelines manual available on DaveNet (Corp. 9351−L9), or contact the Technical Support Department Product Ap- plication group for assistance.

NOTE − For new or replacement line set installation, refer to Service and Application Note − Corp. 9112−L4 (C−91−4).

TABLE 1

REFRIGERANT LINE SET

Models

Liquid

Vapor/

L15 Line Set

 

Line

Suction

 

 

 

Line

 

 

 

 

 

−024, −036

3/8 (10)

7/8 (22)

L15 line set sizes are

and−048

 

 

dependent on unit match up.

 

 

 

See XP21 Engineering

 

 

 

Handbook to determine

 

 

 

correct line set sizes.

 

 

 

 

−060

3/8 (10)

1−1/8

Field Fabricated

 

 

 

 

NOTE

 

 

 

1−1/8" adapter.

 

 

 

 

 

 

Page 3

XC21 SERIES

Page 3
Image 3
Lennox International Inc Dave Lennox Signature Collection XC21 System installation instructions Placement