XC21 Field Operational Checklist
|
| Cooling*** |
|
| Heating*** |
|
|
|
|
|
|
|
|
Unit Readings | Y1 | Expected results | Y2 | Y1 | Expected results | Y2 Second |
| First | during Y2 demand | Second | during Y2 demand | ||
| First Stage | Stage | ||||
| Stage | (toggle switch ON) | Stage | (toggle switch ON) | ||
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Compressor |
|
|
|
|
|
|
|
|
|
|
|
|
|
Voltage |
| Same |
|
| Same |
|
|
|
|
|
|
|
|
Amperage |
| Higher |
|
| Higher |
|
|
|
|
|
|
|
|
Condenser Fan motor |
|
|
|
|
|
|
|
|
|
|
|
|
|
Amperage |
| Same or Higher |
|
| Same or Higher |
|
|
|
|
|
|
|
|
Temperature |
|
|
|
|
|
|
|
|
|
|
|
|
|
Ambient |
| Same |
|
| Same |
|
|
|
|
|
|
|
|
Outdoor Coil Discharge Air |
| Higher |
|
| Lower |
|
|
|
|
|
|
|
|
Compressor Discharge Line |
| Higher |
|
| Higher |
|
|
|
|
|
|
|
|
Indoor Return Air |
| Same |
|
| Same |
|
|
|
|
|
|
|
|
Indoor Coil Discharge Air |
| Lower |
|
| Higher |
|
|
|
|
|
|
|
|
Pressures |
|
|
|
|
|
|
|
|
|
|
|
|
|
Suction (Vapor) |
| Lower |
|
| Down |
|
|
|
|
|
|
|
|
Liquid |
| Higher |
|
| Higher |
|
|
|
|
|
|
|
|
Note − Unit may have a low ambient control or control that locks in second−stage operation below its set point. It may be necessary to remove a wire from the control when performing this check.
** On the XC21 units, the System Operation Monitor controls the second−stage solenoid coil in compressor.
*** Cooling Mode Operation − Block outdoor coil to maintain a minimum of 375 psig during testing.
Page 17
XC21 SERIES