XC21 Field Operational Checklist

XC21 Field Operational Checklist

 

 

Cooling***

 

 

Heating***

 

 

 

 

 

 

 

 

Unit Readings

Y1

Expected results

Y2

Y1

Expected results

Y2 Second

 

First

during Y2 demand

Second

during Y2 demand

 

First Stage

Stage

 

Stage

(toggle switch ON)

Stage

(toggle switch ON)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Compressor

 

 

 

 

 

 

 

 

 

 

 

 

 

Voltage

 

Same

 

 

Same

 

 

 

 

 

 

 

 

Amperage

 

Higher

 

 

Higher

 

 

 

 

 

 

 

 

Condenser Fan motor

 

 

 

 

 

 

 

 

 

 

 

 

 

Amperage

 

Same or Higher

 

 

Same or Higher

 

 

 

 

 

 

 

 

Temperature

 

 

 

 

 

 

 

 

 

 

 

 

 

Ambient

 

Same

 

 

Same

 

 

 

 

 

 

 

 

Outdoor Coil Discharge Air

 

Higher

 

 

Lower

 

 

 

 

 

 

 

 

Compressor Discharge Line

 

Higher

 

 

Higher

 

 

 

 

 

 

 

 

Indoor Return Air

 

Same

 

 

Same

 

 

 

 

 

 

 

 

Indoor Coil Discharge Air

 

Lower

 

 

Higher

 

 

 

 

 

 

 

 

Pressures

 

 

 

 

 

 

 

 

 

 

 

 

 

Suction (Vapor)

 

Lower

 

 

Down

 

 

 

 

 

 

 

 

Liquid

 

Higher

 

 

Higher

 

 

 

 

 

 

 

 

Note − Unit may have a low ambient control or control that locks in second−stage operation below its set point. It may be necessary to remove a wire from the control when performing this check.

** On the XC21 units, the System Operation Monitor controls the second−stage solenoid coil in compressor.

*** Cooling Mode Operation − Block outdoor coil to maintain a minimum of 375 psig during testing.