3.7) SETTING THE PRESSURE CONTROLS (Continued)

LG-10 thru LG-30 - User Manual

Electro-Steam Generator Corp.

3.7) SETTING THE PRESSURE CONTROLS (Continued)

5.At this point the contactor(s) should be clicked off and you should be able to click them on and then off again by pressing the SAFETY RESET. This is a way to test if the “SAFETY” is still controlling the pressure, and not the “CONTROL”. While setting the “SAFETY” and the contactor(s) are off, if the SAFETY RESET does not cause the contactor(s) to click on and off again, INCREASE the setting on the “CONTROL

WARNING DO NOT allow the pressure to exceed the rating on the Safety Valve (#18). If contactor(s) do not turn off before the pressure limit is exceeded, manually shut off generator, open the Steam Out (#16), and DECREASE the pressure setting on the “SAFETY” pressure control. If you cannot get the “SAFETY” to control the pressure, it may need to be replaced.

Pressure Control Settings

 

“Control”

“Safety”

High Pressure

80 PSI

85 PSI

(0-100 PSI)

High Pressure

25 PSI

27 PSI

(0-30 PSI)

Low Pressure

11 PSI

13.5 PSI

(0-15 PSI)

 

 

6.Open the Steam Out (#16) to exhaust some pressure. Continue pressing the SAFETY RESET until the contactor(s) click on and remain on. The pressure should eventually begin to rise. If it doesn’t, throttle the Steam Out (#16) somewhere between closed and open until it does.

7.Pay attention to what the pressure reads when the contactor(s) click off. If the pressure stopped BELOW the “SAFETY PRESSURE SETTING”, then INCREASE the pressure setting on the “SAFETY”. If the pressure stopped ABOVE, then DECREASE the pressure setting.

8.Continue to watch the pressure go up and down, while adjusting the “SAFETY” and pressing the SAFETY RESET, until the pressure stops at the proper “SAFETY PRESSURE SETTING”.

9.At this point the “SAFETY” should be set to the proper “SAFETY PRESSURE SETTING”, and the “CONTROL” should be set somewhere above the “SAFETY.

10.Let the pressure drop below the “OPERATING PRESSURE SETTING” and then press the SAFETY RESET, so that the contactor(s) click on. DECREASE the pressure setting on the “CONTROL” until the contactor(s) click off.

11.Repeat Step 10 until you no longer need to press the SAFETY RESET for the contactor(s) to click on.

12.Continue to watch the pressure go up and down, while adjusting the “CONTROL”, until the pressure stops at the proper “OPERATING PRESSURE SETTING”.

13.The Pressure Controls are now set.

NOTE: If at anytime the SAFETY RESET needs to be pressed after the pressure controls are set, either one of the controls are bad, the “SAFETY” is set too low, or the “CONTROL” is set too high.