4.) CALCULATIONS AND DATA SHEETS
4.1) HEATER POWER & VOLTAGE RATINGS
LG Model units use 3 Heaters to meet the required (KW) POWER from the customer’s
specified INPUT VOLTAGE. Each heater comes in 5 different (KW) POWER RATINGS and 4 different VOLTAGE RATINGS.
AVAILABLE HEATER RATINGS
KW |
| VOLTAGES |
| |
3.33 | 208 | 240 | 480 | 600 |
5.00 | 208 | 230 | 480 | 600 |
6.50 | 208 | 230 | 480 | 600 |
8.33 | 214 | 240 | 480 | 600 |
9.75 | 208 | 240 | 480 | 600 |
POWER RATINGS per MODEL
MODEL UNIT | QUAN. | KW |
3 | 3.33 | |
3 | 5.00 | |
3 | 6.50 | |
3 | 8.33 | |
3 | 9.75 |
HEATER VOLTAGE RATINGS per INPUT VOLTAGE (VOLTS)
Input Voltage | 208 | 220 | 230 | 240 | 380 | 400 | 415 | 425 | 440 | 460 | 480 | 550 | 575 | 600 |
208 | 208 | 240 | 240 | 208 | 240 | 240 | 240 | 480 | 480 | 480 | 600 | 600 | 600 | |
208 | 230 | 230 | 230 | 208 | 230 | 230 | 230 | 480 | 480 | 480 | 600 | 600 | 600 | |
208 | 230 | 230 | 230 | 208 | 230 | 230 | 230 | 480 | 480 | 480 | 600 | 600 | 600 | |
214 | 214 | 240 | 240 | 214 | 214 | 240 | 240 | 480 | 480 | 480 | 600 | 600 | 600 | |
208 | 208 | 240 | 240 | 208 | 240 | 240 | 240 | 480 | 480 | 480 | 600 | 600 | 600 |
NOTE:
4.2) TOTAL POWER RATING CALCULATIONS
The HEATER POWER RATING and NUMBER OF HEATERS are used to calculate the TOTAL POWER RATING. Since the HEATER POWER RATINGS are in Kilowatts, they must be multiplied by 1000 to convert them to Watts.
DEFINITIONS:
PT = Total Power Rating
PH = Heater Power Rating
xH = Number of Heaters
MODEL UNIT |
|
|
|
|
|
Heater Power Rating (Watts) | 3,333 | 5,000 | 6,500 | 8,333 | 9,750 |
X Number of Heaters | 3 | 3 | 3 | 3 | 3 |
Total Power Rating (Watts) | 10,000 | 15,000 | 19,500 | 25,000 | 29,250 |
| 15 of 33 |
|
|
|
|