Test run

Test run

Selfdiagnosisfunction

Error display

This function displays the self diagnosis and the type of error if identified.

For the error display, the applicable code is displayed on the 7 segment LED on the wired remote controller and AHU controller.

If there are 2 or more errors simultaneously, the codes are displayed in the order of occurrence.

Once you resolve the error, the error code will disappear.

Error display method

The first display on the 7 segment display refers to the error code and the second part refers to the location information of the communication PCB address or sensor location. Refer to the following for details.

Error type

Display condition

Example of output

Detail description

 

 

 

 

Basic error

CH [Error code] 0

CH30

Error #3

 

 

 

 

Communication PCB error

CH [Error code] [Address]

CH204

Error #2 in communication PCB with

 

 

 

address of ‘#4’

 

 

 

 

Sensor error

CH [Error code] [Location]

CH1302

Air supply temperature sensor error

 

 

 

 

Outdoor unit error

CH [Error code] [Address]

CH17304

Error #173 on the outdoor unit connected

 

 

 

to communication PCB with address of ‘#4’

 

 

 

 

* The address the communication PCB refers to the rotary switch number on the communication PCB.

Location number

Location name

Applicable sensor type

01

RA

Temperature sensor, humidity sensor

 

 

 

02

SA

Temperature sensor, humidity sensor

 

 

 

03

OA

Temperature sensor, humidity sensor

 

 

 

04

Mixing

Temperature sensor

 

 

 

05

Differential pressure

Differential pressure sensor

 

 

 

06

Static pressure

Static pressure sensor

 

 

 

* The above table shows the information of the attached location by sensor.