Error display (AHU)

‘##’ refers to the address information of the communication PCB.

Display

Error item

Cause of error

Cause or error

number

 

 

 

CH

2

##

Temperature sensor

Communication PCB

Temperature sensor disconnection or short circuit at pipe inlet

 

 

 

error at pipe inlet of

rotary switch number

of indoor unit

 

 

 

indoor unit

##

 

CH

3

00

Communication error

 

No communication signal for more than 3 minutes from wired

 

 

 

between wired remote

-

remote controller to the AHU controller

 

 

 

controller and AHU

 

 

 

 

 

controller

 

 

CH

4

##

Communication error

Communication PCB

No communication signal for more than 3 minutes from

 

 

 

between AHU

rotary switch number

communication PCB to AHU controller

 

 

 

controller and

##

 

 

 

 

communication PCB

 

 

CH

5

##

Communication error

Communication PCB

No communication signal for 5 minutes continuously from

 

 

 

between

rotary switch number

communication PCB to outdoor unit

 

 

 

communication PCB

##

 

 

 

 

and outdoor unit

 

 

CH

6

##

Temperature sensor

Communication PCB

Temperature sensor disconnection or short circuit on pipe

 

 

 

error on pipe outlet of

rotary switch number

outlet of indoor unit

 

 

 

indoor unit

##

 

CH

8

00

Emergency operation

-

The operating status of the smoke control mode through smoke detector is displayed

CH

13

01

Temperature sensor

RA

Temperature sensor (RA/SA/Mixing) disconnection/short

 

 

 

error

 

circuit/misconnection or when the sensor value is in the error

 

 

02

 

SA

range

 

 

04

 

Mixing

 

CH

14

01

Humidity sensor error

RA

Humidity sensor (RA/SA/OA) disconnection/short

 

 

02

 

SA

circuit/misconnection or when the sensor value is in the error

 

 

03

 

OA

range

CH

15

00

CO2 sensor error

-

CO2 sensor disconnection/short circuit/misconnection or when

 

 

 

 

 

the sensor value is in the error range

CH

16

05

Pressure sensor error

Differential pressure

Pressure sensor (Differential pressure, static pressure) disconnection/short

 

 

06

 

Static pressure

circuit/misconnection or when the sensor value is in the error range

CH

17

01

Air flow sensor error

RA

Air flow sensor (RA, SA) disconnection/short circuit/misconnection

 

 

02

 

SA

or when the sensor value is in the error range

 

 

 

 

 

 

32AHU CONTROL KIT