Major Components
7
4.0 MAJOR COMPONENTS
The Liebert GXT2-10000RT208 is composed of three major assemblies to provide easier handling,
installation and versatility.

4.1 Main Frame and Electronics

This 6U cabinet arrives without internal batteries to lighten the UPS for easier installation. Once the
cabinet has been placed in its final floor or rack position, the internal batteries may be installed. The
UPS is shipped with standard hardwire terminal blocks for input and output connections.
Figure 1 10 kVA Dual Inverter Liebert GXT2-10000RT208, front and rear views

4.2 Internal Battery Pack

The center front bezel may be pulled forward and removed to reveal the battery access plate. The
cover plate can be removed by extracting the three screws at the top of the cover plate and lifting the
plate off. The two internal battery packs are compact assemblies ready to slide into the battery com-
partment after the front battery access plate has been removed. Electrical connection is made with
the two slotted battery connectors.
Figure 2 Internal battery pack and connector
!
UPStation GXT
Status Indicators
and Controls
Front Bezels, 3
Battery Compartment
(behind center and right bezels); Internal
Battery Pack is shipped loose
(see Section 4.2)
Hardwire
Knockouts
Liebert
IntelliSlot® Port
Cooling Fan,
1 of 3
REPO
Switch
External Battery
Connectors
DB-9
Communications
Ports, 2
Input Circuit
Breaker
Output
Circuit
Breaker
UPS/Bypass
Breaker
REAR VIEW
FRONT VIEW
Battery connector
on front of battery pack
DISCONTINUED
PROD U C T