Installation and Configuration
14
6.3 Connect Input/Output Power
The UPS has hardwire terminal blocks for input and output electrical connections. Optional output
distribution modules permit connecting additional loads to the UPS. These optional plug-and-play
distribution modules offer different types and numbers of connection plugs.

6.3.1 Distribution Module Electrical Connections

Electrical connections are made through a removable conduit box that attaches to the rear of the
UPS.
The installer must provide a 60A branch circuit breaker. The input circuit breaker and the output cir-
cuit breaker on the rear fixed-panel of the UPS disconnect all power between the main cabinet and
the distribution box.
The manual bypass switch passes utility power directly to the bypass switch from the input terminal
block. The input circuit breaker does not disconnect power from the manual bypass switch.
Figure 6 60A branch circuit breaker connection diagram
!WARNING
The UPS must be completely powered down before beginning to make these electrical
connections.
!CAUTION
A disconnect switch shall be provided by others for ac input circuit. To reduce the risk of fire,
connect only to a circuit provided with branch circuit overcurrent protection for 60 amperes
rating in accordance with the National Electric Code, ANSI/NFPA 70.
!CAUTION
A disconnect switch shall be provided by others for ac output circuit. To reduce the risk of fire,
connect only to a circuit provided with branch circuit overcurrent protection for 60 amperes
rating in accordance with the National Electric Code, ANSI/NFPA 70.
Optional
Output
Distribution
Plate
Utility
Input
60A External
Branch
Circuit Breaker
60A
Input
Circuit
Breaker
Output
Terminal
Block
60A
Output
Circuit
Breaker
60A Main tenance
Bypass Breaker

UPS

Input
Indicator
Output
Indicator
DISCONTINUED
PROD U C T