Maintenance

12.0MAINTENANCE

The Liebert GXT2-10000RT208 requires very little maintenance. The batteries are valve-regulated, non-spillable, flame retardant, lead acid and should be kept charged to obtain their design life. The UPS continuously charges the batteries when connected to the utility supply.

When storing the UPS for any length of time, it is essential to plug the UPS in for at least 24 hours every four to six months to ensure full recharge of the batteries. Failure to recharge the batteries peri- odically will permanently degrade battery capacity.

The Liebert GXT2-10000RT208 is designed to allow the user to safely replace the internal batteries. Read the safety cautions before proceeding. Contact your local dealer or Liebert representative to obtain the appropriate replacement battery kit part number and pricing.

12.1Battery Replacement

! CAUTION

A battery can present a risk of electrical shock and high short circuit current. The following precautions should be observed before replacing the batteries:

Remove rings, watches and other metal objects.

Use a Phillips (crosshead) screwdriver with insulated grips.

Do not lay tools or other metal objects on top of the batteries.

If the battery replacement kit is damaged in any way or shows signs of leakage, contact your local dealer or Liebert representative immediately.

Do not dispose of batteries in a fire. The batteries may explode.

12.1.1Internal Battery Replacement Procedures

Both battery packs should be replaced at the same time.

1.

Gently remove the front center plastic bezel

 

 

cover from the UPS by pulling forward.

UPS

2.

Loosen the three screws on the front battery

 

 

cover grille. Lay the battery cover grille aside for

 

 

reassembly.

 

3.

Remove the battery brackets at the bottom front

Battery

 

of the battery pack.

 

4.

Grasp each battery pack assembly individually

 

 

and pull each out of the front of the UPS. Be

 

 

prepared to support the weight of the battery as

 

 

it is withdrawn.

 

5.

Unpack the new battery assemblies taking care

 

 

not to destroy the packing. Compare new and

 

old battery assemblies to make sure they are the same. If so, proceed with the next step. If they are different, STOP and contact your local dealer, Liebert representative or the Liebert Worldwide Support Group.

6.Line up and slide in the new replacement battery packs.

7.Reinstall the brackets on the front of the battery pack.

8.Reconnect the slotted battery cable connectors.

9.Reattach the front battery door, tightening the two screws.

10.Reattach the front plastic bezel to the UPS.

Battery

Cover

Front Bezels

NOTE

These are hot-swappable replacement batteries. However, caution should be exercised because during this procedure the load is unprotected from disturbances and power outages.

35

DISCONTINUED

 

PRODUCT

Page 41
Image 41
Liebert GXT2-10000RT208 user manual Maintenance, Internal Battery Replacement Procedures, Battery Cover Front Bezels

GXT2-10000RT208 specifications

The Liebert GXT2-10000RT208 is a highly sophisticated uninterruptible power supply (UPS) designed to deliver reliable power protection for critical IT infrastructure and business operations. With a power capacity of 10,000 VA, this UPS ensures the continuous operation of essential devices, safeguarding them from potential damage caused by power interruptions, surges, or sags.

One of the standout features of the Liebert GXT2-10000RT208 is its online double conversion technology. This technology provides a consistent, high-quality power output by converting incoming AC power to DC and then back to AC. This process eliminates voltage fluctuations and offers a stable energy supply, ensuring that connected equipment operates smoothly, regardless of the condition of the utility power.

The UPS is designed to support a wide range of applications, making it an ideal choice for data centers, telecommunications setups, and other critical environments. Its advanced microprocessor control ensures precise monitoring and regulation of power conditions. The Liebert GXT2-10000RT208 also features an impressive input voltage range, which is beneficial in areas where power quality is inconsistent.

Equipped with an LCD display, users can easily access vital information regarding the UPS’s operational status, battery health, and power protection levels. This user-friendly interface simplifies monitoring and management, allowing for quick assessments and troubleshooting.

Another key characteristic of the Liebert GXT2-10000RT208 is its modular design. This allows for easy installation and maintenance, as well as the opportunity to expand the power capacity by adding external battery cabinets. This scalability ensures that businesses can adapt their power protection solutions to meet evolving needs without significant changes to their existing setups.

The UPS also includes advanced battery management features that optimize battery lifespan and performance. The Liebert GXT2-10000RT208 employs intelligent charging algorithms and battery testing functions to ensure reliable performance when needed most. Furthermore, support for various communication protocols enhances compatibility with other management systems, enabling seamless integration into existing infrastructure.

In summary, the Liebert GXT2-10000RT208 is a powerful and versatile UPS solution that combines advanced technology with robust features. Its online double conversion technology, extensive monitoring capabilities, and scalable design make it an excellent choice for organizations seeking reliable protection for their critical systems. With the GXT2-10000RT208, businesses can operate confidently, knowing their power supply is secure from unexpected disruptions.