Lincoln 1117-000-A Burner Blower Motor, Visually check to see if motor is running. If not

Models: 1117-000-A 1100ADVSVC

1 36
Download 36 pages 40.03 Kb
Page 9
Image 9

 

Burner Blower Motor

Visually check to see if motor is running. If not,

 

 

check for 120 VAC to motor at motor connector (wire

 

 

#5 and #22). If voltage is not present, trace wiring

 

 

back to fan switch. If voltage is present and motor is

 

 

not running, check for opens, shorts, or grounds.

 

 

Also, WITH POWER OFF: check for locked rotor.

 

Transformer, Burner

Primary is 120 VAC with 24 VAC secondary. If 120

 

 

VAC is not present, trace wiring back to Main Fan

 

 

Centrifugal Switch. If 120 VAC is present, check for

 

 

24 VAC at secondary of transformer. If no voltage is

 

 

present, replace transformer.

 

Centrifugal Switch of Burner

Check of 120 VAC at motor connector, on wire #13

 

Blower Motor

to neutral. If voltage is not present, trace wiring back

 

 

to transformer. If voltage is not present and motor is

 

 

running, replace the burner blower motor.

 

Ignition Control

24 volts should be present at 24 volt terminals. If not

 

 

present, trace wiring back to centrifugal switch.

 

 

When 24 VAC is supplied, the control switches 120

 

 

VAC from L1 and L2 to the hot surface ignitor. if 120

 

 

VAC is not present at L1 and L2, trace wiring

 

 

back to fan switch. If 24 VAC and 120 VAC are

 

 

present and 120 VAC is not across the hot surface

 

 

ignitor terminals, replace the ignition control.

 

Hot Surface Ignitor

If 120 VAC is present at hot surface ignitor terminals,

 

 

visually check to see that the ignitor is heating.

 

 

(Ignitor may be viewed through the port glass in end

 

 

of burner tube.) The ignitor should glow bright red.

 

 

If the ignitor does not heat, replace the ignitor.

 

Ignition Control

After 45 seconds of hot surface ignitor pre-heat, the

 

 

ignition control will switch 24 VAC to the gas control

 

 

valves. Check for 24 VAC output from ignition

 

 

control, across terminals marked "valve" and "valve

 

 

ground". If no voltage is present, replace ignition

 

 

control.

 

Gas Control Valves

When 24 VAC is supplied to the gas control valve,

 

 

the valve should open. Check for gas pressure at

 

 

the manifold tap located just before the burner. If

 

 

there is no pressure, check the incoming gas supply

 

 

to be sure all manual valves are open and flexible

 

 

gas hose is properly connected. If gas is present

 

 

and coils of gas valve are energized, the gas valve is

 

 

probably defective.

Flame will not stay lit

Hot Surface Ignitor

Six seconds after the gas valve opens, ignition must

 

 

occur. if flame is not detected, the ignition control

 

 

will shut off and lock out. To reset the ignition

 

 

control, turn off the burner switch for 45 seconds,

 

 

then turn on the burner switch to retry ignition. The

 

 

ignition control requires a minimum of 0.8 D.C.

 

 

microamps. To check flame sensing operation,

 

 

connect a digital multimeter (capable of measuring

 

 

D.C. micro-amps) between the "ground" terminal on

 

 

ignition control and the ground lead.

 

 

NOTE: This is a current measurement and the

 

 

meter must be connected in series. If these

 

 

readings are not achieved, replace the hot surface

 

 

ignitor.

 

 

NOTE: The D.C. micro amp test must be conducted

 

 

with the oven in low flame (bypass) operation. Turn

 

 

the temperature control to the lowest setting.

Impinger II –Advantage Service Manual - Domestic

9

Page 9
Image 9
Lincoln 1117-000-A Burner Blower Motor, Visually check to see if motor is running. If not, Transformer, Burner, control