Lincoln 1155-000-EA achieved, replace ignition control, connections, NOTE Flame should be on at

Models: 1155-000-EA 1164-000-EA 1154-000-EA

1 32
Download 32 pages 63.63 Kb
Page 11
Image 11

 

 

 

shorts. Readings should be as follows, V1 – 2.9K ohms

 

 

 

 

approx., V2 – 1.3K ohms approx. If these readings are

 

 

 

 

not achieved, replace gas valve. If these readings are

 

 

 

 

achieved, replace ignition control.

 

 

Flame will not stay on

Flame sensor

To check for flame sensor operation, connect a digital

 

 

 

 

multimeter (capable of measuring DC microamps)

 

 

 

 

between the flame sensor wire and the flame sensor

 

 

 

 

connection on the ignition control. Sensor current is to

 

 

 

 

be 0.9 microamps, minimum. If these readings are not

 

 

 

 

achieved, replace igniter/sensor assembly. Also check

 

 

 

 

for any type of damage to flame sensor wire and

 

 

 

 

connections.

 

 

 

 

NOTE: The DC microamp test must be conducted with

 

 

 

 

the oven in low flame (bypass) operation.

 

 

 

Power supply

Set the temperature to the lowest temperature setting.

 

 

 

 

If there is sufficient microamp current, but the flame will

 

 

 

 

not stay lit, check for proper polarity of the power

 

 

 

 

supply.

 

 

 

Ignition control

If there is sufficient microamp current, and there is

 

 

 

 

proper polarity of the power supply, but the burner will

 

 

 

 

not stay lit, check the reset button on the ignition

 

 

 

 

control. If the above test is okay, replace the ignition

 

 

 

 

control.

 

 

 

NOTE: Flame should be on at

 

 

 

 

this time

 

 

 

Low flame is on, but

Control transformer

Check for supply voltage to the primary of control

 

 

no main flame

 

transformer. If no voltage is present, trace wiring back

 

 

 

 

to oven fan switch. If voltage is present, check for

 

 

 

 

24VAC at transformer secondary. If there is primary

 

 

 

 

voltage, but no secondary voltage, replace control

 

 

 

 

transformer.

 

 

 

Conveyor motor

Check for supply voltage to the conveyor motor at

 

 

 

 

terminal #6 to neutral. If no voltage is present, trace

 

 

 

 

wiring back to the oven fan switch. If voltage is present,

 

 

 

 

but the motor will not run, check the motor windings for

 

 

 

 

opens or shorts. If any of the above fail, replace the

 

 

 

 

conveyor motor.

 

 

 

Capacitor, conveyor motor

Check for shorts or grounds. Replace capacitor as

 

 

 

 

needed.

 

 

 

 

WARNING: Capacitor has a stored charge, discharge

 

 

 

 

before testing.

 

 

 

Switch, conveyor reversing

Check continuity between switch terminals. Replace

 

 

 

 

switch as needed.

 

 

 

Oven control

If there is voltage supplied to the motor, and the motor,

 

 

 

 

capacitor and reversing switch check good, replace the

 

 

 

 

oven control.

 

 

Conveyor motor runs,

NOTE: Display will indicate

 

 

 

but there is no speed

“BELT JAM”

 

 

 

display

 

 

 

 

 

Oven control

Check for output voltage from oven control to hall effect

 

 

 

 

sensor (sensor is located in the conveyor motor).

 

 

 

 

Measure voltage at the motor connector, red wire and

 

 

 

 

yellow wire. Voltage should be approx. 10VDC. If no

 

 

 

 

voltage is present, trace wiring back to oven control. If

 

 

 

 

there is no voltage output at the oven control, replace

 

 

 

 

oven control.

 

 

 

Conveyor motor

If there is voltage supplied to the hall effect sensor,

 

 

 

 

check for a frequency output from the hall effect

 

 

 

 

sensor. Measure frequency across the yellow and white

 

 

 

 

wires in the motor connector. Frequency reading

 

Impinger II – Advantage Digital Service Manual - International

11

Page 11
Image 11
Lincoln 1155-000-EA achieved, replace ignition control, for any type of damage to flame sensor wire and, connections