Intermittent Heating | Thermal/Overload of | The main fan motors and the burner blower motors are |
| Main Fan and Burner | equipped with internal thermal protection and will cease to |
| Blower Motors | operate if overheating occurs. As the motors overheat and |
|
| then cool, this will cause the units to cycle on and off |
|
| intermittently. Improper ventilation or preventive maintenance |
|
| may cause this. Also, most of the problems listed under |
|
| "Oven will not heat" can cause intermittent failure. |
Conveyor will not run | Voltage Supply | Check incoming voltage supply at line 1 to neutral. There |
|
| should be a voltage reading of 120 VAC. If not present, check |
|
| breakers. |
| Fan Switch | See procedure for checking at beginning of section. |
| 10 Amp Fuse | Check and/or replace. |
| Fuse holder | Check and/or replace. |
| Speed Adjustment | This is a 0 to 10 K ohm, 1 turn potentiometer. With power off, |
| Potentiometer | remove the black and white pot leads from the motor control |
|
| board at terminals P1, P2. Place the meter leads on the black |
|
| lead (P2) and on the white lead (P1). Rotating the pot., slowly, |
|
| from low to high, the meter readings should show an even |
|
| transition from 0 to 10 K ohms ± 5%. There should be no |
|
| dead or open spots through out the 1 turn of the pot. Check |
|
| both leads to ground. There should be no continuity to |
|
| ground. If any of the above checks fail, replace the pot |
| DC Motor Control | Check for 120 VAC input to the control board at terminals L1 |
| Board | and L2. If not present, check wiring back to the fuse. If 120 |
|
| VAC is present at L1 and L2, check both fuses on control |
|
| board (8A line and 1A armature), check the VDC output at |
|
| terminals A+ and |
|
| and L2, and DC voltage is present A+ and |
|
| not run, check gear motor as follows. |
| Conveyor Gear Motor | If DC voltage is present at A+ and A- and the motor does not |
|
| run, first check the mini breaker and then the conveyor. Refer |
|
| to the next possible cause. Check the leads to the motor for |
|
| evidence of any shorts or opens, and each lead to ground. |
|
| Check motor brushes. From the top of the motor, rotate motor |
|
| shaft to determine if there is a locked rotor or a locked gear |
|
| box (use care so magnet and H.S. board are not damaged). |
|
| Replace motor as needed. |
| Conveyor | Check for any mechanical misalignment. Also, check for worn |
|
| bearings. A conveyor belt that is over tightened will cause |
|
| excessive bearing wear and sometimes, irregular speed. |
Low Profile – | 7 |