SEQUENCE OF OPERATIONS
MODEL
MODEL
POWER SUPPLY
Electrical power to be supplied to the oven by a three conductor service.
Brown conductor is hot
Blue conductor is neutral.
Green conductor is ground.
CONTROL BOX
AUTO COOL DOWN
When the temperature in either one of the control boxes reaches 120°F ±3° (49°C ± 1.7° ) , the cooling fan thermostats will switch power to the cooling fans . The thermostats will interrupt power to the cooling fans when the temperature falls to 100°F ± 3° (37°C ± 1.7° )
MAIN FAN CIRCUIT
Line voltage is permanently supplied to a normally open contact of the oven power switch. Line voltage is permanently supplied to the two normally open cooling fan thermostats, a normally open contact of the oven power relay. Closing the oven power switch supplies line voltage to oven power relay, its contacts now close, supplying line voltage to the two main fan motors and the two burner circuits. Closing the oven power switch also supplies line voltage to the control box cooling fans, the temp. display, and the conveyor circuit.
BURNER CIRCUIT
NOTE: This oven utilizes two complete burner/ temperature control systems. The sequence of operations is the same for each system.
Closing the main fan switch supplies line voltage, through the oven power relay, through a three amp. fuse, through the gas pressure switch, through the main fan air pressure switch through the oven cavity
TEMPERATURE CONTROL
Closing the oven power switch supplies line voltage, through the oven power relay, through a three amp. fuse, through the gas pressure switch, through the main fan air pressure switch through the oven cavity
CONVEYOR DRIVE
Closing the oven power switch supplies line voltage, through the oven power relay, through the electromagnetic filter to the conveyor control. AC volts are converted to DC volts and are supplied to the conveyor motor at terminals A+ and
Low Profile – 1600 Advantage Series Service Manual – International | 3 |