Lincoln 1634-000-EA replace the spark generator. If there, or damaged wires in burner tube

Models: 1633-000-EA 1634-000-EA

1 32
Download 32 pages 28.27 Kb
Page 8
Image 8

 

 

replace the spark generator. If there

 

 

is visible damage to the igniter/sensor

 

 

assembly, replace. Also check for frayed

 

 

or damaged wires in burner tube.

 

Gas valve

Check for supply voltage to gas valve.

 

 

If there is no voltage present, check

 

 

reset button, check all connections for

 

 

tightness. If there still is no voltage at

 

 

gas valve, replace ignition control.

 

 

If there is voltage present, check for

 

 

gas pressure at gas pressure tap located

 

 

in gas piping at burner manifold.

 

 

If there is no gas pressure, replace

 

 

gas valve.

Flame will not stay on

Flame sensor

To check for flame sensor operation,

 

 

connect a digital multimeter (capable

 

 

of measuring D.C. micro amps) in

 

 

series with the flame sensor wire and

 

 

ignition control. Sensor current is 3

 

 

micro amps D.C. minimum.

 

 

NOTE: The D.C. micro amp test must

 

 

be conducted with the oven in low

 

 

flame (bypass) operation. Turn the

 

 

temperature control to its lowest

 

 

setting. If these readings are not

 

 

achieved, replace igniter/sensor assy.

 

 

Also, check for any type of damage to

 

 

flame sensor wire and connections.

 

Ignition control

If there is sufficient flame sensor current,

 

 

but the burner will not remain ignited,

 

 

check the reset button on ignition control.

 

 

NOTE: Check for proper polarity of

 

 

the power supply. If all of the above

 

 

are OK, replace ignition control.

Pilot lamp is on,

Temperature control

Check for supply voltage across

But no main flame

 

terminals L2 and 240 on temperature

 

 

control board. If no voltage is present,

 

 

check wiring back to hi-limit thermostat.

 

 

Turn the temperature adjustment knob to

 

 

the maximum temperature position and

 

 

check for supply voltage at the load

 

 

terminal #7 and #8. If voltage is present

 

 

and unit is not heating, refer to

 

 

“temperature regulation valve” for next

 

 

check. If voltage is not present, proceed.

 

Thermocouple probe

With power on and thermocouple leads

 

 

attached to board, measure the millivolt

 

 

out put of the thermocouple. Refer to the

 

 

thermocouple chart in section D for

 

 

proper readings.

 

Temperature control

WITH POWER OFF: Remove the

 

Potentiometer

potentiometer leads from the temperature

 

 

control board. Place ohm meter test leads

 

 

on the blue and green pot leads. Reading

 

 

should be 1 K ohms. Place meter leads

 

 

across the blue and purple pot leads and

 

 

rotate knob from high to low. Repeat on

 

 

green and purple leads. Check for even

 

 

rise and fall of ohms reading to insure

 

 

that there are no open or dead spots in

 

 

the potentiometer. Check each lead to

 

 

ground for shorts. Replace potentiometer

8

Low Profile – 1600 Advantage Series Service Manual – International

Page 8
Image 8
Lincoln 1634-000-EA replace the spark generator. If there, is visible damage to the igniter/sensor, Gas valve, gas valve