| On at this time | control at terminals #13 and #12. Of there is no voltage, |
| Electronic temperature | trace wiring back to the burner switch. Also check for |
| control | supply voltage to terminal #20 on the electronic |
|
| temperature control. If there is no voltage at terminal |
|
| #20, trace wiring back to terminal #13. Set temperature |
|
| control to maximum temperature and check for output |
|
| voltage at terminal #21 and neutral. If voltage is present |
|
| at terminal #20 and neutral, and the unit is not heating, |
|
| refer to “Temperature regulation valve” for next check. |
|
| If voltage is not present, proceed. |
| Thermocouple probe | WITH POWER ON AND THERMOCOUPLE LEADS |
|
| ATTACHED TO THE ELECTRONIC TEMPERATURE |
|
| CONTROL: Measure the D.C. millivolt output of these |
|
| leads. Refer to chart in the “Removal, Installation and |
|
| Adjustment” section for proper readings. If these |
|
| readings are not achieved, replace thermocouple. |
| Burner control. | Check for supply voltage to main valve. If no voltage is |
|
| present, trace wiring back to burner control. If there is |
|
| no voltage output, replace burner control. |
| Main gas valve | Check for supply voltage to main valve. If there is |
|
| voltage present, check to see that valve is opening. |
|
| Connect manometer to pressure tap on outlet side of |
|
| valve. If there is voltage to the valve, but no output gas |
|
| pressure, replace the valve. |
| Temperature regulation valve | If supply voltage is present on the electronic |
|
| temperature control, terminal #13 to neutral, check for |
|
| voltage at temperature regulation valve. If no voltage is |
|
| present, trace wiring back to electronic temperature |
|
| control, terminal #20. If voltage is present, listen for |
|
| valve to open and close. Also check for opens or shorts |
|
| in the operating coil. Replace temperature regulation |
|
| valve as needed. |
Intermittent heating | Thermal/Overload of main fan | The main fan motor and burner blower motor are |
| and burner blower motors | equipped with internal thermal protection and will cease |
|
| to operate if overheating occurs. As the motors over- |
|
| heat and then cool, this will cause the units to cycle on |
|
| and off intermittently. Improper ventilation or lack of |
|
| preventive maintenance may cause this. Also, most of |
|
| the problems listed under “Oven will not heat” can |
|
| cause intermittent failure. |
Conveyor will not run | NOTE: The ovens may contain | two, three or four conveyor drive systems using like |
| components. The trouble shooting sequence will be the same for each of the conveyor | |
| drive systems |
|
|
|
|
| Power supply | Check circuit breakers, reset if required. Check power |
|
| plug to be sure it is firmly in receptacle. Measure |
|
| incoming power, call power co. if needed. |
| Switch, oven fan | Check continuity between switch terminals. Replace |
|
| switch as needed. |
| Relay, main fan | Check for supply voltage to relay terminal #13. If |
|
| voltage is not present, trace wiring back to power |
|
| supply. If voltage is present, check for supply voltage at |
|
| terminal #14. If there is no voltage at terminal #14, and |
|
| the relay is energized, replace the main fan relay. |
| Fuse, 2 Amp | Check, replace if necessary. |
| Fuse holder | Check for supply voltage to fuse holder. If no voltage is |
|
| present, trace wiring back to main fan relay. Check fuse |
|
| holder, replace if necessary. |
| Switch, conveyor | Check for supply voltage to conveyor switch. If no |
|
| voltage is present, trace wiring back to fuse holder. |
|
| Check continuity between switch terminals. Replace |
14 |
| Impinger X2 – Analog Service Manual – Dom & Int’l |